Inspections for the day of: Thursday, August 10, 2006.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-02095 ELE-Aging Inspection8/10/20068/10/20068/10/2006 4:27:35 PM DONE
called contr and asked that he call for final since he says he is done
ELE06-02956 Temporary Service8/10/20068/10/20068/10/2006 3:50:45 PMPFAIL
Scheduled by a contractor via Hello! on 8/10/2006 at 8:22:47 AM. Contact: ###-####. called, left message, left corr notice, nec 110.26(A) work space about equipment shall be provided,BCC Job id shall be posted, Address shall be posted, Access to grounding electrode shall be provided, fee due
ELE06-02704 Electrical Rough-In8/10/20068/10/20068/10/2006 2:34:48 PMPPART
Please inspect underslab conduit.; Phone #: ###-#### Internet Inspection Request from: Jim Friend so part c wing ok to cover under slab
ELE06-02823 Final8/10/20068/10/20068/10/2006 1:58:31 PMPFAIL
Internet Inspection Request from: Tyler Bowen called, left corr notice, nec 408.4 circuit directory shall be clear, concise, and complete as to its purpose, BCC no violations shall be retained, strap all conduit coming out bottom of panel
ELE06-01678 Final8/10/20068/10/20068/10/2006 1:12:04 PMPFAIL
garage code 1234 lock box on front door code is 4718; Phone #: ###-#### Internet Inspection Request from: Todd Holbrook called left corr notice, nec 110.26(F)(1)&(2) there shall be no foreign systems in dedicated electrical space(panel and meter) (clearance shall be maintained), 406.4(D) after installation, recpt faces shall be flush with or project from faceplates, 404.9(A) switch faceplates shall seat against finished surface
ELE06-02903 Final8/9/20068/10/20068/10/2006 11:43:40 AMAPASS
Work performed by Kyle Sharp.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz ok to final
ELE06-01153 Final8/10/20068/10/20068/10/2006 9:51:15 AMAPASS
garage code is 6309; Phone #: ###-#### Internet Inspection Request from: Cevyn Recla called, left survey, nec 210.8(A)(7) laundry room recpt shall be gfci since less than 6' from sink
ELE06-02910 Final8/9/20068/10/20068/10/2006 9:31:24 AMAPASS
Chuck; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to final
ELE06-02910 Permanent Service8/10/20068/10/20068/10/2006 9:30:56 AMAPASS
Chuck; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt p/s u/g rec ok
ELE06-02909 Final8/9/20068/10/20068/10/2006 9:22:49 AMAPASS
Chuck; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to final
ELE06-02909 Permanent Service8/10/20068/10/20068/10/2006 9:22:07 AMAPASS
Chuck; Phone #: ###-#### Internet Inspection Request from: Cathy p/s u/g rec ok
ELE06-02930 Electrical Rough-In8/10/20068/10/20068/10/2006 8:34:21 AMAPASS
Can you call me a 1/2 to hour before so I can make sure that you have access to the residence. Thank you; Phone #: ###-#### Internet Inspection Request from: Robert Murray ric ok
ELE06-02355 Electrical Rough-In8/9/20068/10/20068/10/2006 8:09:22 AMAPASS
daryl - grid insp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called contr, ok to cover ceiling only