Inspections for the day of: Thursday, August 10, 2006.
Number of inspections: 10
Percentage of inspections complete: 90 %
Percentage of inspections not complete: 10 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00037 INSP-Final Inspection8/2/20068/3/2006 P 
bob; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
FIR05-00612 FIR-Aging Inspection8/10/20068/10/20068/15/2006 10:44:14 AM DEFR
FIR06-00162 INSP-Final Inspection8/10/20068/10/20068/11/2006 9:08:44 AMPPASS
Fire alarm passed final field inspection.
BLD06-01044 FIRE-Conference8/10/20068/10/20068/11/2006 9:08:08 AMPDONE
On site confrence with the electrical contractor to discuss exit signage and requirements for emergency lighting.
FIR06-00251 INSP-Sprinkler Rough-in/Hydro8/8/20068/10/20068/11/2006 9:05:49 AMPPART
OH rough-in at the new addition is acceptable for cover, noted one head at the north entry hallway is overspaced from the wall and will need relocated. AG hydro for the addition passed.
FIR06-00321 INSP-Final Inspection8/8/20068/10/20068/10/2006 2:39:36 PMPPASS
Fire sprinkler passed final inspection, permit finaled.
FIR06-00129 INSP-Final Inspection8/9/20068/10/20068/10/2006 11:46:54 AMAPART
Partial alarm inspection only for 5 SD and notification devices in the east portion of remodel area, DH at main corridor not installed at this time, remainder of devices on circut to be tested when completed.
BLD06-01553 FIRE-Final Inspection8/10/20068/10/20068/10/2006 10:45:45 AMPFAIL
Need to provide one PFE in the storage room, relocate one exit sign/emergency light to the north exit door at new corridor, provide fire alarm notification for the new exit corridor and storage room which will require a FA permit.
FIR06-00480 INSP-Final Inspection8/9/20068/10/20068/10/2006 10:38:42 AMAPASS
Fire sprinkler permit finaled.
BLD04-02464 FIRE-Sprinkler Rough-in8/9/20068/10/20068/10/2006 10:02:02 AMAFAIL
Forest, This is an inspection for the fire riser underground and thrust blocking at bldg A-1, I did not know exactly what inspection that was listed under. Thanks, Todd; Phone #: ###-#### Internet Inspection Request from: Todd Kurns NOTE: No sprinkler permit related to the UG work could be located, notified contractor of possible work without permit.