Inspections for the day of: Friday, August 10, 2007.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01796 ELE-Aging Inspection8/10/20078/10/20078/17/2007 3:59:29 PM NR
suc
ELE07-02432 Final8/10/20078/10/20078/10/2007 3:35:28 PMPPASS
mike Phone #: ###-####
ELE07-02796 Permanent Service8/10/20078/10/20078/10/2007 3:03:48 PMPFAIL
mike Phone #: ###-####
raise mast so clearance over pool is 22.5 ft
ELE07-02797 Permanent Service8/10/20078/10/20078/10/2007 2:23:16 PMPFAIL
paul Phone #: ###-####
requires 18 ft over alley
house to be disconnected from garage power when changeover takes place. violations in sub panel will be corrected also.
ELE07-00928 Conference8/10/20078/10/20078/10/2007 1:32:32 PMPPART
david Phone #: ###-####
talked about j box/gutter 24 in nipple deration and raintight
ELE07-00573 Electrical Rough-In8/9/20078/10/20078/10/2007 12:46:29 PMAPART
Scheduled by a contractor via Hello! on 8/9/2007 at 11:53:48 AM. Contact: ###-####.
hard lids ANOP
ELE07-02791 Electrical Rough-In8/9/20078/10/20078/10/2007 11:47:23 AMAPART
Inspection to cover eaves and soffits only, not the interior of building. Phone #: ###-#### Internet Inspection Request from: Trent Reagan
ok to cover eaves and soffits only
ELE07-00079 Electrical Rough-In8/9/20078/10/20078/10/2007 11:08:45 AMAPASS
This is for electrical rough on building #2. Call Lonnie at ###-#### with any questions. Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa
ELE07-02018 Permanent Service8/9/20078/10/20078/10/2007 10:11:33 AMAPART
Paul; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
underground to house ok
ELE07-02789 Rough-In Permanent Service8/9/20078/10/20078/10/2007 9:46:15 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: DJ Carman
Underground covered without inspection.
no electrode at house.
gas pipe under house panel.
box-fill.
sheath not into box.
6 in free conductor.
Id #6 neutral.
staple romex within 8 in.
grounds have no approved connection.