Inspections for the day of: Friday, August 10, 2007.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-01669 ELE-Aging Inspection8/10/20078/10/20078/13/2007 9:52:59 AM DONE
no sign per description, suc
ELE07-01088 Electrical Rough-In8/9/20078/10/20078/10/2007 3:32:50 PMPPASS
shawn - underground Phone #: ###-#### ok to pour anop, 2nd floor, west
ELE07-02620 Rough-In Permanent Service8/10/20078/10/20078/10/2007 3:01:34 PMPPASS
corrections made Phone #: ###-#### Internet Inspection Request from: Celinda Winters coorr made, ric ok p/s o/h rec ok
ELE07-02760 Rough-In Permanent Service8/10/20078/10/20078/10/2007 2:20:21 PMPCANC
butch - underground Phone #: ###-#### wrong type request, see ri
ELE07-02760 Electrical Rough-In8/10/20078/10/20078/10/2007 2:20:05 PMPPASS
butch - underground Phone #: ###-#### u/g ok to cover
ELE07-02794 Permanent Service8/10/20078/10/20078/10/2007 1:27:07 PMPFAIL
###-#### mike called, left message, left corr notice, nec 250.24(A) gec shall connect to grounded service conductor at service, 250.52(A)(1) shall connect to water pipe within 5' of entering building,250.53(D)(2) shall supplement water pipe with ground rods, 404.8 center of operating handle of breaker shall not be over 6'-7" above floor, 230.24(A) service drop conductors shall be 8' above roof
ELE07-02765 Final8/10/20078/10/20078/10/2007 12:34:42 PMPPASS
Doug, called 1st for access; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt told owner to finish bkr labels, ok to final
ELE07-02760 Rough-In Permanent Service8/10/20078/10/20078/10/2007 11:51:07 AMACANC
Scheduled by a contractor via Hello! on 8/10/2007 at 7:10:23 AM. Contact: ###-####. contr asked to cancel
ELE07-01690 Final8/9/20078/10/20078/10/2007 11:50:13 AMAPASS
mike Phone #: ###-#### ok to final
ELE06-03714 Permanent Service8/9/20078/10/20078/10/2007 10:26:28 AMAFAIL
matt Phone #: ###-#### met owner, left corr notice, 110.3(A) shall use only suitable electrical material, not water pipe ell at service, 250.24(A) shall install grounding and conductors to grounded service conductor at service, 250.52(A)(1) shall connect to water pipe within 5' of entering building, 250.53(D)(2) shall supplenent water pipe with ground rods, 344.30 shall support rigid pipe within 3' of conduit termination
ELE06-03834 Final8/9/20078/10/20078/10/2007 9:25:42 AMAPASS
pat Phone #: ###-#### called contr to reset gfci, ok to final
ELE07-02106 Final8/9/20078/10/20078/10/2007 8:30:53 AMAPASS
Tim; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to final
ELE07-02398 Electrical Rough-In8/9/20078/10/20078/10/2007 7:47:21 AMAPART
matt Phone #: ###-#### tub area only ok to cover, will see wall ltr