ELE07-01669
| ELE-Aging Inspection | 8/10/2007 | 8/10/2007 | 8/13/2007 9:52:59 AM | | DONE |
|
|
no sign per description, suc
|
ELE07-01088
| Electrical Rough-In | 8/9/2007 | 8/10/2007 | 8/10/2007 3:32:50 PM | P | PASS |
|
|
shawn - underground Phone #: ###-#### ok to pour anop, 2nd floor, west
|
ELE07-02620
| Rough-In Permanent Service | 8/10/2007 | 8/10/2007 | 8/10/2007 3:01:34 PM | P | PASS |
|
|
corrections made Phone #: ###-#### Internet Inspection Request from: Celinda Winters coorr made, ric ok p/s o/h rec ok
|
ELE07-02760
| Rough-In Permanent Service | 8/10/2007 | 8/10/2007 | 8/10/2007 2:20:21 PM | P | CANC |
|
|
butch - underground Phone #: ###-#### wrong type request, see ri
|
ELE07-02760
| Electrical Rough-In | 8/10/2007 | 8/10/2007 | 8/10/2007 2:20:05 PM | P | PASS |
|
|
butch - underground Phone #: ###-#### u/g ok to cover
|
ELE07-02794
| Permanent Service | 8/10/2007 | 8/10/2007 | 8/10/2007 1:27:07 PM | P | FAIL |
|
|
###-#### mike called, left message, left corr notice, nec 250.24(A) gec shall connect to grounded service conductor at service, 250.52(A)(1) shall connect to water pipe within 5' of entering building,250.53(D)(2) shall supplement water pipe with ground rods, 404.8 center of operating handle of breaker shall not be over 6'-7" above floor, 230.24(A) service drop conductors shall be 8' above roof
|
ELE07-02765
| Final | 8/10/2007 | 8/10/2007 | 8/10/2007 12:34:42 PM | P | PASS |
|
|
Doug, called 1st for access; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt told owner to finish bkr labels, ok to final
|
ELE07-02760
| Rough-In Permanent Service | 8/10/2007 | 8/10/2007 | 8/10/2007 11:51:07 AM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 8/10/2007 at 7:10:23 AM. Contact: ###-####. contr asked to cancel
|
ELE07-01690
| Final | 8/9/2007 | 8/10/2007 | 8/10/2007 11:50:13 AM | A | PASS |
|
|
mike Phone #: ###-#### ok to final
|
ELE06-03714
| Permanent Service | 8/9/2007 | 8/10/2007 | 8/10/2007 10:26:28 AM | A | FAIL |
|
|
matt Phone #: ###-#### met owner, left corr notice, 110.3(A) shall use only suitable electrical material, not water pipe ell at service, 250.24(A) shall install grounding and conductors to grounded service conductor at service, 250.52(A)(1) shall connect to water pipe within 5' of entering building, 250.53(D)(2) shall supplenent water pipe with ground rods, 344.30 shall support rigid pipe within 3' of conduit termination
|
ELE06-03834
| Final | 8/9/2007 | 8/10/2007 | 8/10/2007 9:25:42 AM | A | PASS |
|
|
pat Phone #: ###-#### called contr to reset gfci, ok to final
|
ELE07-02106
| Final | 8/9/2007 | 8/10/2007 | 8/10/2007 8:30:53 AM | A | PASS |
|
|
Tim; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to final
|
ELE07-02398
| Electrical Rough-In | 8/9/2007 | 8/10/2007 | 8/10/2007 7:47:21 AM | A | PART |
|
|
matt Phone #: ###-#### tub area only ok to cover, will see wall ltr
|