BLD05-02204
| FIRE-Final Inspection | 8/10/2007 | 8/10/2007 | 8/13/2007 9:15:16 AM | P | PASS |
|
|
Fire life safety finaled.
|
FIR07-00482
| INSP-Sprinkler Rough-in/Hydro | 8/7/2007 | 8/10/2007 | 8/10/2007 4:15:16 PM | P | DEFR |
|
|
Rescheduled per discussion with contractor.
|
FIR07-00460
| INSP-Final Inspection | 8/8/2007 | 8/10/2007 | 8/10/2007 3:45:00 PM | A | FAIL |
|
|
Items # 1,2,and 6 on the previously issued correction notice remain to be fully addressed.
|
FIR07-00267
| INSP-Final Inspection | 8/10/2007 | 8/10/2007 | 8/10/2007 2:30:13 PM | P | PASS |
|
|
Corrections made, fire alarm permit finaled.
|
FIR07-00474
| INSP-Sprinkler Rough-in/Hydro | 8/9/2007 | 8/10/2007 | 8/10/2007 2:12:08 PM | P | FAIL |
|
|
Pneumatic testing failed due to 3 1/2 psi pressure loss at the guage.
|
FIR07-00482
| INSP-Final Inspection | 8/7/2007 | 8/10/2007 | 8/10/2007 1:50:55 PM | P | NR |
|
|
Need to test sprinkler monitoring and alarm via project related FA permit prior to final approval.
|
FIR07-00493
| INSP-Final Inspection | 8/10/2007 | 8/10/2007 | 8/10/2007 1:40:26 PM | P | PASS |
|
|
c/n items repaired, fire sprinkler permit finaled.
|
FIR07-00572
| INSP-Sprinkler Rough-in | 8/10/2007 | 8/10/2007 | 8/10/2007 1:32:20 PM | P | FAIL |
|
|
Inspection concluded after 1st and 2nd floors due to the excessive number of defficiencies including overspaced heads, blocked heads, missing retaining straps at beam clamps, mixed temp. heads, mixed k-factors, missing hangers, heads in need of adjustment at drop ceilngs, some heads are still covered with painters tape and paper, etc.
|
FIR07-00316
| INSP-Sprinkler Rough-in/Hydro | 8/9/2007 | 8/10/2007 | 8/10/2007 12:51:05 PM | A | FAIL |
|
|
UG fire supply line hydrostatic test failed due to 15psi. pressure loss at the guage.
|
FIR07-00446
| INSP-Sprinkler Rough-in | 8/9/2007 | 8/10/2007 | 8/10/2007 12:05:40 PM | A | CANC |
|
|
Inspection rescheduled per phone call from contractor.
|
FIR07-00243
| INSP-Sprinkler Rough-in/Hydro | 8/9/2007 | 8/10/2007 | 8/10/2007 12:04:34 PM | A | PART |
|
|
Heads at the laundry chute are okay for cover, noted one hanger at the 2nd floor piping to the chute in need of attatchment.
|
FIR07-00592
| INSP-Sprinkler Rough-in/Hydro | 8/10/2007 | 8/10/2007 | 8/10/2007 11:46:35 AM | P | PART |
|
|
Items noted at previous inspection have been completed, overhead FS piping is acceptable for cover.
|
FIR07-00618
| INSP-Sprinkler Rough-in/Hydro | 8/9/2007 | 8/10/2007 | 8/10/2007 11:33:17 AM | A | PART |
|
|
OH rough-in at the drop ceilings is approved for cover. Also discussed exit signage and emergency lighting with the on site electrician.
|
MIS07-00151
| FIR-Final | 8/9/2007 | 8/10/2007 | 8/10/2007 11:31:39 AM | A | FAIL |
|
|
Need verification of a current annual inspection by a licensed fire sprinkler contractor for the existing fire sprinkler system, doors and hardware at several locations in the back office areas are missing and will need to be installed for verification of code compliance, provide means to test EM lighting at the sales floor and stock area.
|
FIR05-00536
| INSP-Sprinkler Rough-in | 8/10/2007 | 8/10/2007 | 8/10/2007 11:27:23 AM | A | PART |
|
|
OH rough-in is approved as noted for shell areas on the 6th and 7th floors see sheets FP 22,23,24,25 on stamped resubmittals, three rooms as noted on each floor no access provided, one area each floor needs to have the temp. walls removed to eliminate obstruction issues for shell system protection.
|