FIR11-00200
| INSP-Final Inspection | 8/10/2011 | 8/10/2011 | 8/12/2011 10:22:04 AM | P | PEND |
|
|
Acceptance test and permit final pending provision for conditions indicated per NFPA 750 sec. 7.8.1.5 (valve identification), 7.8.1.8 (valve supervision), 7.9.2.4 (alarms), IFC 904.3.5 (monitoring), and NFPA 25 13.3.1.3.(control valves in water-based fire protection systems). Valves on connections to water supplies, sectional control and isolation valves, and other valves in supply pipes to nozzles and other fixed water-based fire suppression systems shall be supervised (1)-(4). 7.9.2.4.2- Trouble and supervisory signals shall include operation of monitored valving.
|
FIR11-00308
| INSP-Final Inspection | 8/9/2011 | 8/10/2011 | 8/10/2011 3:46:27 PM | A | PART |
|
|
Begin 24 hr. air test of the new dry system piping at 11:30 AM @44.5psig.
|
FIR11-00336
| INSP-Final Inspection | 8/9/2011 | 8/10/2011 | 8/10/2011 3:40:27 PM | P | PASS |
|
|
Fire alarm work passed inspection. Permit final approved.
|
FIR11-00246
| INSP-Final Inspection | 8/8/2011 | 8/10/2011 | 8/10/2011 3:38:55 PM | P | PASS |
|
|
Scope of fire sprinkler work passed inspection. Permit finaled.
|
BLD11-00969
| FIRE-Final Inspection | 8/9/2011 | 8/10/2011 | 8/10/2011 3:36:08 PM | A | PASS |
|
|
Fire life safety finaled.
|
FIR11-00246
| INSP-Final Inspection | 8/5/2011 | 8/10/2011 | 8/8/2011 11:15:33 AM | A | CANC |
|
|
Requesting final inspection Wed. morning. Please call Trent one hr before inspection time @ ###-####. Phone #: ###-#### >> Inspection requested via web by Trent Bice Inspection cancelled from web by: Trent Bice
|