Inspections for the day of: Friday, August 10, 2012.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD12-00636 FIRE-Final Inspection8/9/20128/10/20128/13/2012 7:16:39 AMACANC
To be rescheduled per Chris Phone #: ###-####
FIR12-00406 INSP-Sprinkler Rough-in8/10/20128/10/20128/10/2012 3:28:06 PMPPASS
Sprinkler piping can be covered.
BLD12-01188 FIRE-Final Inspection8/9/20128/10/20128/10/2012 3:25:54 PMAFAIL
Prior to a temporary occupancy being given for the vestibule door all interior door hardware needs to be installed and inspection tags provided on all of the fire extinguishers.
FIR12-00371 INSP-Sprinkler Rough-in8/9/20128/10/20128/10/2012 3:24:29 PMAFAIL
Pendant heads and upright heads are located too close to one another in two locations as marked on the plans. The dry pendants need to be foamed. Remove tape/paper from the upright heads. The control valve to the anti-freeze system has been shut for an unknown reason. The sprinkler heads SIN number installed does not match what was submitted. Information needs to be submitted for the change.
FIR12-00396 INSP-Sprinkler Rough-in8/10/20128/10/20128/10/2012 2:36:19 PMPFAIL
Sprinkler piping can not be covered. Two pendant heads have not been changed to the quick responce type, one changed head is leaking water on the floor, the remains of full height walls are blocking upright sprinkler heads in two locations, I need access to the riser room and above room 131 to verify upright sprinkler coverage, system needs to be hydro tested and the existing insulation that is located at the roof deck is hanging down and blocking upright sprinkler heads in several locations. See the redlined city approved plans.
BLD11-01269 FIRE-Final Inspection8/9/20128/10/20128/10/2012 12:49:23 PMAPART
Life safety has passed in area "C" first and second floors. To final this building the signage needs to be provided at the fire control room doors and the fire alarm permit finaled.
FIR12-00376 INSP-Final Inspection8/10/20128/10/20128/10/2012 12:22:35 PMPCANC
Rand Gruber Phone #: ###-#### >> Inspection requested via web by Rand D. Gruber Inspection cancelled from web by: Rand D. Gruber
FIR11-00543 INSP-Sprinkler Rough-in/Hydro8/9/20128/10/20128/10/2012 9:36:25 AMPCANC
Need a Hydro Inspection Fri 8.10 hoping for 2PM - Tyler Miller is he contact at ###-#### Phone #: ###-#### >> Inspection requested via web by Kindel de Leon Inspection cancelled from web by: Kindel de Leon