FIR18-00208
| INSP-Final Inspection | 8/10/2018 | 8/10/2018 | 8/10/2018 3:11:09 PM | P | PASS |
|
|
Fianl fire sprinkler inspection complete.
|
FIR18-00448
| INSP-Final Inspection | 8/9/2018 | 8/10/2018 | 8/10/2018 2:56:02 PM | P | FAIL |
|
|
Three heads in clean room are overspace @ 144 square feet, heads need to be relocated to 130 square feet or less. Pass-through section between clean room and hallway requires fire sprinklers to be installed per conversation with Tim Frost Fire sprinkler plan reviewer.
Call Anthony to coordinate Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR18-00448
| INSP-Sprinkler Rough-in/Hydro | 8/9/2018 | 8/10/2018 | 8/10/2018 2:48:19 PM | P | DONE |
|
|
Hydrostatic test for newly installed overhead fire sprinkler piping witnessed, no pressure loss observed at contractor provided gauge.
Call Anthony to coordinate Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR18-00627
| INSP-Final Inspection | 8/10/2018 | 8/10/2018 | 8/10/2018 1:01:22 PM | P | PASS |
|
|
Final commercial hood suppression inspection complete.
Dave Phone #: ###-####
|
NAF17-00074
| INSP-Final | 8/8/2018 | 8/10/2018 | 8/10/2018 12:26:08 PM | P | DONE |
|
|
No fire sprinklers, no fire alarms, fuel pumps are existing, fire extinguishers are placed with current inspection tags. Final life fire safety inspection complete.
Call prior to going Phone #: 2089892465 >> Inspection requested via mobile web by Brad
|
BLD17-01499
| FIRE-Final Inspection | 8/10/2018 | 8/10/2018 | 8/10/2018 12:12:47 PM | P | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection complete.
|
FIR17-00542
| INSP-Sprinkler Rough-in/Hydro | 8/10/2018 | 8/10/2018 | 8/10/2018 12:11:53 PM | A | PASS |
|
|
Final underground supply inspection complete.
|
NAF18-00055
| INSP-Final | 8/10/2018 | 8/10/2018 | 8/10/2018 11:47:35 AM | P | DONE |
|
|
Previously noted items have been completed, Ron Johnson with Boise Fire approved the 18 foot wide gate opening to remain, fire extinguishers are placed with current inspection tags. Final life fire safety inspection complete.
Phone #: 2088301685 >> Inspection requested via mobile web by Brandon
|
BLD17-04596
| FIRE-Final Inspection | 8/10/2018 | 8/10/2018 | 8/10/2018 11:15:31 AM | P | PART |
|
|
Project is being worked in phases, fire sprinklers complete for phase 1 (East side of level 7), fire alarms complete for phase 1, fire extinguisher are placed with current inspection tags, final life fire safety inspection for phase 1 east side complete, west side to be inspected at a later date.
Final life safety // Zac Phone #: ###-####
|
NAF18-00099
| INSP-Final | 8/9/2018 | 8/10/2018 | 8/10/2018 11:12:57 AM | A | DONE |
|
|
Final fire alarm inspection complete.
Phone #: ###-#### Inspection requested via web by Robert Gobler
|
NAF18-00058
| INSP-Final | 8/9/2018 | 8/10/2018 | 8/10/2018 11:12:21 AM | A | DONE |
|
|
Final fire alarm inspection complete.
Phone #: ###-#### Inspection requested via web by Robert Gobler
|
NAF18-00060
| INSP-Final | 8/10/2018 | 8/10/2018 | 8/10/2018 10:47:58 AM | A | DONE |
|
|
Final fire alarm inspection complete.
|
NAF18-00007
| INSP-Final | 8/10/2018 | 8/10/2018 | 8/10/2018 10:47:38 AM | A | DONE |
|
|
Final life fire safety inspection complete.
|
NAF18-00103
| INSP-Final | 8/9/2018 | 8/10/2018 | 8/10/2018 10:40:45 AM | A | DONE |
|
|
Final commercial hood fire suppression inspection complete.
Call prior to going Phone #: 2086088402 >> Inspection requested via mobile web by Dave
|
FIR18-00021
| INSP-Sprinkler Rough-in | 8/9/2018 | 8/10/2018 | 8/10/2018 9:21:21 AM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping located above hardlids on level 1 complete, notated the city approved drawings with pink highlighter areas approved for cover.
George Jess is the contact for this inspection. He is request a Hard Lid inspection in the bathrooms. He is hoping for an appointment in the AM. We appreciate your help with this. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD17-04615
| FIRE-Final Inspection | 8/9/2018 | 8/10/2018 | 8/10/2018 8:24:02 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection complete.
Brian Phone #: ###-####
|
FIR18-00598
| INSP-Sprinkler Rough-in | 8/9/2018 | 8/10/2018 | 8/10/2018 8:11:58 AM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, area of work approved for cover.
Tom Phone #: ###-####
|
FIR18-00391
| INSP-Final Inspection | 8/9/2018 | 8/10/2018 | 8/10/2018 7:25:47 AM | A | PART |
|
|
Fire alarm inspection complete for east side of tenant space, remaining items for fire alarm system on west side to be inspected at a later date.
Contact is Dirk. Requested time for inspection is 7am if possible. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|