ELE97-02634
| INSP - T/S and Final | 8/8/1997 | 8/11/1997 | 8/12/1997 12:00:00 AM | A | PASS |
|
|
08/11/97 403 -
|
ELE97-02655
| INSP - Ele Rough-In/Perm Svc | 8/8/1997 | 8/11/1997 | 8/11/1997 12:00:00 AM | A | PASS |
|
|
08/11/97 403 -
|
ELE97-00430
| INSP - Electrical Rough-In | 8/8/1997 | 8/11/1997 | 8/11/1997 12:00:00 AM | A | PART |
|
|
08/10/97 403 - pool penthouse and intermediate wall lobby r/i LOBBY AREA NOT READY, WILL RESCHEDULE.
|
ELE97-02316
| INSP - Electrical Rough-In | 8/8/1997 | 8/11/1997 | 8/11/1997 12:00:00 AM | A | FAIL |
|
|
NEC:210-23(A)(1). DISHWASHER, DISPOSAL, AND MICRO-WAVE ON SEPERATE CIRCUITS. NEC: 210-52(B). AT LEAST 2 SMALL APPLIANCE BRANCH CIRCUITS REQUIRED, LIVING ROOM NOT INCLUDED ON KITCHEN CIRCUITS...MB
|
ELE97-01299
| INSP - Permanent service | 8/11/1997 | 8/11/1997 | 8/11/1997 12:00:00 AM | P | NR |
|
|
08/11/97 403 - ADDED SERVICE TO PERMIT/8/11/97/PE WILL RESCHEDULE...MB
|
ELE97-01299
| INSP - Final | 8/11/1997 | 8/11/1997 | 8/11/1997 12:00:00 AM | P | NR |
|
|
08/11/97 403 - I HAVE SERV. ON SEPERATE INSPECTION FOR TODAY, AND THEN T WILL RESCHEDULE...MB
|
ELE97-02662
| INSP - Ele Rough-In/Perm Svc | 8/11/1997 | 8/11/1997 | 8/11/1997 12:00:00 AM | P | PASS |
|
|
08/11/97 403 -
|
ELE97-02664
| INSP - T/S and Final | 8/11/1997 | 8/11/1997 | 8/11/1997 12:00:00 AM | P | FAIL |
|
|
08/11/97 403 - NEC: 230-78. SHALL BE NO EXPOSED LIVE PARTS IN SERVICE EQ 110-12(C). BROKEN RECEPTICLE IN TEMPORARY POWER POLE.
|