Inspections for the day of: Thursday, August 11, 2005.
Number of inspections: 22
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00428 INSP-Sprinkler Rough-in8/11/20058/11/20058/12/2005 8:48:11 AMPPART
Sprinkler rough-in as shown on the city plans is ok. Pendant head at north entry into large room needs to match existing. Earth quake bracing is lacking in the north end. Per the approved plans, Design Hazard/Limitiations, this permit shall meet the minimum requirements of the International FIre Code. The entire sprinkler system shall meet the code requirements under which it was installed and if it doesn't it must be brought up to current code. This is for all aspects of the sprinkler system including but not limited to hangers, EQ bracing and sprinkler spacing.
FIR05-00380 INSP-Final Inspection8/11/20058/11/20058/12/2005 7:54:19 AMPPASS
fire sprinkler finaled
BLD03-02236 FIRE-Final Inspection8/11/20058/11/20058/11/2005 3:32:13 PMPFAIL
repair emergency lights and provide the canopies for the sprinkler pendants. final fire alrm permit
FIR04-00737 INSP-Sprinkler Rough-in/Hydro8/11/20058/11/20058/11/2005 3:16:01 PMPPASS
Wet system hydro test passed
BLD05-01583 FIRE-Final Inspection8/11/20058/11/20058/11/2005 3:14:57 PMPPART
A temporary occupancy was given until I can investigate the requirement for audio/visual alarms.
BLD05-01583 FIRE-Final Inspection8/11/20058/11/20058/11/2005 3:11:05 PMPCANC
duplicate inspection
BLD04-00556 FIRE-Final Inspection8/11/20058/11/20058/11/2005 1:35:44 PMPPASS
Life safety finaled
FIR05-00443 INSP-Sprinkler Rough-in8/11/20058/11/20058/11/2005 1:35:17 PMPFAIL
The existing sidewall heads above the ceiling are blocked by new duct work. Additional heads and resubmittals are required. I told the contractor that I was ok with the school opening as long as this work area was not accessible.
FIR04-00376 FIR-Aging Inspection8/11/20058/11/20058/11/2005 12:47:35 PM NR
work in progress
FIR04-00375 FIR-Aging Inspection8/11/20058/11/20058/11/2005 12:47:09 PM NR
work in progress
FIR04-00374 FIR-Aging Inspection8/11/20058/11/20058/11/2005 12:46:12 PM NR
work in progress
FIR05-00155 INSP-Sprinkler Rough-in/Hydro8/10/20058/11/20058/11/2005 12:31:44 PMPFAIL
Overhead hydro test failed. System lost 4 lbs
FIR05-00016 INSP-Sprinkler Rough-in/Hydro8/10/20058/11/20058/11/2005 12:30:15 PMPPASS
Underground supply line hydro test passed
BLD04-01909 FIRE-Conference8/11/20058/11/20058/11/2005 12:27:08 PMPDONE
I marked up sheet C1.0 on the approved drawings in red for the curbing that needs to be painted to show the fire dept access routes.
FIR03-00737 INSP-Final Inspection8/11/20058/11/20058/11/2005 11:46:10 AMPFAIL
dave; Phone #: ###-#### Provide map at the facp and repair/test both phone lines since they did not provide trouble when disconnected.
FIR05-00432 INSP-Final Inspection8/10/20058/11/20058/11/2005 11:00:25 AMAPASS
Fire alarm permit finaled
BLD04-02934 FIRE-Conference8/10/20058/11/20058/11/2005 10:59:57 AMADONE
Per sam rogers a temp would be acceptable if the existing fire alarm system provided adequate sound levels in the remodeled area. All other life safety items would need to be provided prior to the temporary occupancy being given
BLD04-02767 FIRE-Conference8/11/20058/11/20058/11/2005 10:59:38 AMPDONE
Per sam rogers a temp would be acceptable if the existing fire alarm system provided adequate sound levels in the remodeled area. All other life safety items would need to be provided prior to the temporary occupancy being given
FIR05-00210 INSP-Conference8/11/20058/11/20058/11/2005 10:59:19 AMPDONE
Per sam rogers a temp would be acceptable if the existing fire alarm system provided adequate sound levels in the remodeled area. All other life safety items would need to be provided prior to the temporary occupancy being given
FIR05-00363 INSP-Alarm Testing8/10/20058/11/20058/11/2005 9:12:28 AMAPASS
Fire alarm finaled
FIR05-00363 INSP-Final Inspection8/11/20058/11/20058/11/2005 9:12:09 AMPPASS
Fire alarm finaled
BLD05-01220 FIRE-Final Inspection8/10/20058/11/20058/11/2005 8:36:08 AMAPART
robert; Phone #: ###-#### Inspection was for the smoke evac system. It operated correctly from the two spot type smoke detectors located at the two front exit/entrance. I also inspected the exit signs and emergency lights. They passed as well. I notified the general contractor that the door to the lab with the keyed deadbolt is not approved type of hardware.