ELE06-02968
| Rough-In Permanent Service | 8/10/2006 | 8/11/2006 | 8/11/2006 4:27:12 PM | P | CANC |
|
|
brad-call prior to insp ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley see ri and p/s
|
ELE06-02968
| Permanent Service | 8/11/2006 | 8/11/2006 | 8/11/2006 4:02:20 PM | P | NR |
|
|
brad-call prior to insp ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley storm kept ipco from having time to pull meter, will do next week
|
ELE06-02968
| Electrical Rough-In | 8/11/2006 | 8/11/2006 | 8/11/2006 4:01:09 PM | P | PASS |
|
|
brad-call prior to insp ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley 2 rooms ric ok
|
ELE06-02978
| Temporary Service | 8/11/2006 | 8/11/2006 | 8/11/2006 3:58:29 PM | P | PASS |
|
|
daryl; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley t/s u/g n ok
|
ELE06-00319
| Electrical Rough-In | 8/10/2006 | 8/11/2006 | 8/11/2006 3:09:52 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: JENNY EMEL ri exterior walls ok
|
ELE06-02627
| Final | 8/11/2006 | 8/11/2006 | 8/11/2006 3:01:32 PM | P | NH |
|
|
Aaron; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt no addres posted
|
ELE06-02429
| Final | 8/11/2006 | 8/11/2006 | 8/11/2006 2:01:43 PM | P | PART |
|
|
kevin; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles reviewed gfci change and light globe required with elect, rest of inside ok, need to do outside lights only
|
ELE06-02956
| Temporary Service | 8/11/2006 | 8/11/2006 | 8/11/2006 1:49:19 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 8/11/2006 at 8:30:12 AM. Contact: ###-####. corrections not made
|
ELE06-02961
| Final | 8/11/2006 | 8/11/2006 | 8/11/2006 1:12:47 PM | P | PASS |
|
|
after 12:00pm please; Phone #: ###-#### Internet Inspection Request from: Shane Vigil corrections made, survey nec 680.26(B)(5) bond metal pipe for moved light fixture, ok to final
|
ELE06-02095
| Final | 8/10/2006 | 8/11/2006 | 8/11/2006 11:42:48 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 8/10/2006 at 4:44:09 PM. Contact: ###-####. survey to contr for disconnect, brkr closures, and circuit id, ok to final
|
ELE06-01310
| Final | 8/10/2006 | 8/11/2006 | 8/11/2006 10:32:59 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 8/10/2006 at 2:58:59 PM. Contact: ###-####. called, left corr notice, nec 410.4(D) fixture in tub area (3' horizontally) shall be listed for damp location(master bath), 406.8(C) recpt shall not be installed in tub area(master bath), 406.5 recpt faceplates shall cover opening and seat against mounting surface (island,kitchen), 406.4 kitchen counter recpt shall be securely fastened in place, 314.21 drywall shall be repaired around boxes( compactor and range)
|
ELE06-02962
| Permanent Service | 8/10/2006 | 8/11/2006 | 8/11/2006 10:15:43 AM | A | PASS |
|
|
installed new 100amp panel, Any questions call Andy @###-#### Internet Inspection Request from: Andy Rose p/s o/h rec ok
|
ELE06-02793
| Permanent Service | 8/10/2006 | 8/11/2006 | 8/11/2006 10:14:49 AM | A | PASS |
|
|
trent; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley p/s exst meter pak n ok
|
ELE06-02961
| Final | 8/10/2006 | 8/11/2006 | 8/11/2006 9:02:15 AM | A | FAIL |
|
|
please call if you have questions. hot tub; Phone #: ###-#### Internet Inspection Request from: Shane Vigil called contr, left corr notice, nec 680.22(A)(3) recpt shall not be over 20' from inside wall of pool and not less than 10', 680.22(B)(3) existing fixture less than 5' from inside wall of pool shall be gfci protected
|
ELE06-00113
| Electrical Rough-In | 8/10/2006 | 8/11/2006 | 8/11/2006 8:26:20 AM | A | PART |
|
|
Contact: Greg Pack -Hallway ceiling inspection 6th & 7th floors; Phone #: ###-#### Internet Inspection Request from: Deb McCoy 6,7 floor hall clgs anop ok to cover
|