FIR05-00613
| FIR-Aging Inspection | 8/11/2006 | 8/11/2006 | 8/15/2006 10:44:28 AM | | DEFR |
|
|
|
FIR06-00460
| INSP-Final Inspection | 8/11/2006 | 8/11/2006 | 8/11/2006 4:44:00 PM | P | PASS |
|
|
Fire alarm work is acceptable, inspection passed.
|
BLD05-02304
| FIRE-Final Inspection | 8/9/2006 | 8/11/2006 | 8/11/2006 4:42:37 PM | A | NR |
|
|
Per phone call from contractor the project is not completed for inspection at this time.
|
FIR06-00520
| INSP-Final Inspection | 8/10/2006 | 8/11/2006 | 8/11/2006 4:40:10 PM | A | PASS |
|
|
Fire sprinkler passed final inspection.
|
FIR05-00695
| INSP-Alarm Testing | 8/11/2006 | 8/11/2006 | 8/11/2006 1:34:40 PM | P | NR |
|
|
Entry to document the observance of fire alarm wire installation for the hotel guest rooms without and prior to issuance of a FA permit and approved FA plans. Both the electrical contractor and general contractor have been notified that work is to cease until FA plans have been submitted and approved. Also notified contractors a stop work order will be issued Monday 8/14 unless a permit has been issued or pulled wire removed.
|
BLD05-03144
| FIRE-Final Inspection | 8/10/2006 | 8/11/2006 | 8/11/2006 1:07:45 PM | A | FAIL |
|
|
Need to provide signs or markings prohibiting parking for the fire dept. looped access road per review comments note #5.
|
FIR05-00425
| INSP-Sprinkler Rough-in/Hydro | 8/10/2006 | 8/11/2006 | 8/11/2006 12:22:46 PM | A | PART |
|
|
8th and 9th floor guest room adjacent to the temp. elevator are good for cover.
|
FIR05-00037
| INSP-Final Inspection | 8/10/2006 | 8/11/2006 | 8/11/2006 12:20:31 PM | A | PASS |
|
|
Fire sprinkler inspection passed, permit finaled.
|