Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-00007 FIRE-Final Inspection8/11/20088/11/20088/12/2008 8:29:26 AMPPART
Tested remainder of EM lighting and exit signs-noted two exit signs and two EM lights to be repaired, also noted exit discharge lights at three locations are not functional at areas E,F,&B. See 12 item correction notice left on site for a list of life safety issues to be completed prior to final occupancy approval. Also issued correction notices for fire alarm and sprinkler permits including 8 items for FA and 3 items for FS. Per agreement with the contractor and Deputy Chief D. Hanneman school registration may take place provided the fire watch for area "A" auditorium is maintained and limited access to the remainder of the building is provided.
FIR08-00492 INSP-Final Inspection8/11/20088/11/20088/12/2008 8:05:39 AMPCANC
Inspection rescheduled per phone call from general contractor.
FIR08-00255 INSP-Alarm Testing8/11/20088/11/20088/12/2008 8:04:22 AMAPART
Fire dampers passed testing with the exception of one damper at corridor B01-see plans for location, some items on c/n repaired. Items remaining include EOL voltage testing, provide list of signals recieved, area "A" auditorium is not complete including voice evac., two elevators are not finished, kitchen hood interconnect needs tested, noted two supervisory signals at the FACP due to elevator power loss, need to test nac batteries, provide NFPA 72 Record of Completion documents at final inspection.
FIR07-00606 INSP-Sprinkler Rough-in/Hydro8/11/20088/11/20088/11/2008 2:12:40 PMAPART
Final pending completion of work in area A including classroom A106, prop storage, and the auditorium, also need to provide resubmittals for field changes in pipe routing and added upright and pendent heads in the auditorium.
FIR08-00130 INSP-Final Inspection8/8/20088/11/20088/11/2008 1:08:34 PMPFAIL
Correction items include missing test orfice at the inspectors connection, painted head at the furnace closet, missing escutcheons at two closets, pendent heads at both the upstairs and basement level fireplaces must meet distance requirements per NFPA 13D table 7.5.5.3-also noted on plan set, will test the outside bell at next inspection.
FIR07-00830 INSP-Final Inspection8/11/20088/11/20088/11/2008 11:43:37 AMAPASS
Final fire alarm inspection passed, remainder of devices tested, door closure at one location repaired while on site, field ceiling tile installation at the lab storage room to be verified prior to fire life safety approval. Fire alarm permit finaled.
FIR07-00505 INSP-Final Inspection8/11/20088/11/20088/11/2008 10:11:32 AMAPASS
UG fire supply line permit finaled.
BLD07-03241 FIRE-Conference8/11/20088/11/20088/11/2008 10:08:21 AMADONE
Regarding kitchen hood system install.