Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-01201 FIRE-Final Inspection8/11/20088/11/20088/11/2008 4:09:34 PMPPART
The piping in American Family Insurance, 10494, is ok to cover.
BLD08-00840 FIRE-Final Inspection8/8/20088/11/20088/11/2008 3:52:29 PMAPASS
Fire life safety passed.
FIR08-00397 INSP-Final Inspection8/8/20088/11/20088/11/2008 2:20:11 PMAFAIL
The job site approved plan set was not on the job site. A strobe in the first floor area as marked on the plans is blocked by walls. There are many strobes on the second floor that are overspaced. The fire alarm contractor needs to review the spacing on all of the second floor strobes for code compliance. I pointed out a note on the review comments about the minimum voltage allowed from the fire alarm panel that is to be verified prior to my next inspection. Also plans need to be resubmitted showing the door magnets (access controlled egress doors) and their interconnection to the FACP. Basically no testing was performed.
BLD08-01564 FIRE-Final Inspection8/11/20088/11/20088/11/2008 1:35:51 PMPFAIL
I tried to call Jeff twice but only got voice mail on which I left a message. I went to the school but only found a custodian. No inspection performed.