Inspections for the day of: Wednesday, August 11, 2010.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00169 FIR-Aging Inspection8/11/20108/11/20108/11/2010 2:58:49 PM DONE
Contractor to request site inspection for permit final.
FIR10-00168 FIR-Aging Inspection8/11/20108/11/20108/11/2010 2:58:15 PM DONE
Contractor to request site inspection for permit final.
FIR10-00319 INSP-Final Inspection8/10/20108/11/20108/11/2010 2:53:09 PMPPART
Fire alarm acceptance testing completed satisfactory with the exception of duct smoke detection devices due to installation locations in need of revision.
FIR10-00358 INSP-Final Inspection8/10/20108/11/20108/11/2010 2:49:01 PMPPART
Final pending wall post indicator/butterfly valve interface approval. Remainder of the scope of work passed inspection.
BLD10-00236 FIRE-Conference8/11/20108/11/20108/11/2010 2:46:23 PMPDONE
Regarding item #7 on fire code review notes.
FIR10-00350 INSP-Conference8/10/20108/11/20108/11/2010 2:45:48 PMPPASS
Hood suppression system operated correctly under test conditions. Inspection passed, permit finaled.
BLD10-01116 FIRE-Final Inspection8/11/20108/11/20108/11/2010 2:44:38 PMPFAIL
Post two fire extinguishers per plan annotations, remove one exit sign per review comments and plan resubmittal sheet A4.0, provide exit discharge lighting at the west exit, post address numbers. Remainder of life safety items passed.
FIR10-00371 INSP-Sprinkler Rough-in8/10/20108/11/20108/11/2010 11:50:07 AMAPART
Overhead fire sprinkler work is approved for cover at the drop ceilings in the mens and womens restroom, breakroom and entry hallway. Noted some obstructions to upright heads by ductwork trunk lines above the new office room ceiling- contractor to lower ducts to provide clearance as discussed.