Inspections for the day of: Thursday, August 11, 2011.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD11-01030 FIRE-Final Inspection8/11/20118/11/20118/11/2011 4:14:18 PMPFAIL
Project was not ready for a final inspection due to the project related fire sprinkler permit not being able to be finaled.
FIR11-00095 INSP-Sprinkler Rough-in8/10/20118/11/20118/11/2011 4:13:19 PMAPASS
The piping at the second floor, over the lobby stairs, is ok to cover.
FIR11-00375 INSP-Final Inspection8/10/20118/11/20118/11/2011 2:09:35 PMAFAIL
There is a draft stop, leftover wall top, that is blocking upright sprinkler coverage. This obstruction was not shown on the plans. The upright coverage off of the wall is around 163 sq. ft. Per the hydraulic calculations and the existing upright sprinkler spacing 120 sq. ft. is the max.
FIR11-00398 INSP-Final Inspection8/10/20118/11/20118/11/2011 1:18:56 PMAPASS
Permit finaled
FIR11-00302 INSP-Final Inspection8/9/20118/11/20118/11/2011 12:00:49 PMAFAIL
HVAC units 213 and 214 did not shut down immediately upon detection of smoke. All other devices tested ok.