ELE14-02105
| Conference | 8/8/2014 | 8/11/2014 | 8/11/2014 3:47:15 PM | P | DONE |
|
|
MikePlease call prior to inspection and as late as possible please Phone #: ###-#### Discussed minimum recepticals outlets required for habitable rooms, dedicated circuit for receptical located in bathroom, and NM cable support and secure codes.
|
ELE14-02190
| Temporary Service | 8/11/2014 | 8/11/2014 | 8/11/2014 3:44:46 PM | P | DONE |
|
|
Daryl Phone #: ###-#### Discussed min recepticals required for habitable room, dedicated bathroom receptical circuit, NM secure and support code.
|
ELE14-02191
| Temporary Service | 8/11/2014 | 8/11/2014 | 8/11/2014 1:17:00 PM | P | PASS |
|
|
Daryl Phone #: ###-#### Informed contractor about 6x6 pressure treated pole for overhead temp poles. East pole. t/s o/h n ok
|
ELE14-01978
| Rough-In Permanent Service | 8/11/2014 | 8/11/2014 | 8/11/2014 12:59:12 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Seth Stears Unit 49 rough in ok cover p/s u/g n ok
|
ELE14-01979
| Rough-In Permanent Service | 8/11/2014 | 8/11/2014 | 8/11/2014 12:58:31 PM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Seth Stears Unit 39 rough in ok cover p/s u/g n ok
|
ELE08-02423
| ELE-Aging Inspection | 8/11/2014 | 8/11/2014 | 8/11/2014 12:33:56 PM | | DONE |
|
|
Still under construction
|
ELE12-02164
| ELE-Aging Inspection | 8/11/2014 | 8/11/2014 | 8/11/2014 12:24:31 PM | | DONE |
|
|
Waiting on scheduling.
|
ELE14-01666
| Electrical Rough-In | 8/11/2014 | 8/11/2014 | 8/11/2014 11:44:42 AM | A | PASS |
|
|
###-####-Greg-call prior for access Central east area south space, east area north space wall rough in ok cover
|
ELE14-02124
| Final | 8/5/2014 | 8/11/2014 | 8/11/2014 11:19:22 AM | A | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Clint Tate Needed permenant service
|
ELE14-02124
| Electrical Rough-In | 8/11/2014 | 8/11/2014 | 8/11/2014 11:18:52 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Clint Tate Kitchen area remodelled, new cabinets, opening cut in wall, asked to add 2 receptical locations to comply with minimum receptical serving counter top areas. All wiring fished in. rough in ok
|
ELE14-02124
| Permanent Service | 8/11/2014 | 8/11/2014 | 8/11/2014 11:16:35 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Clint Tate p/s o/h rec ok
|
ELE14-02186
| Conference | 8/8/2014 | 8/11/2014 | 8/11/2014 10:53:30 AM | A | DONE |
|
|
Mitch Phone #: ###-#### Discussed min receptical for counter top space, min circuit for counter and bath recepticals, SOEW used for range will replace with NM cable, panel location not permitted in bathrooms, kitchen and bath receptical circuits shall only kitchen and bath areas only.
|
ELE14-02192
| Rough-In Permanent Service | 8/8/2014 | 8/11/2014 | 8/11/2014 8:55:07 AM | A | PASS |
|
|
Please call when done Phone #: ###-#### Inspection requested via web by Thomas wilson Rough in ok cover p/s u/g rec ok
|