Inspections for the day of: Tuesday, August 11, 2015.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00783 INSP-Final Inspection8/11/20158/11/20158/11/2015 3:48:30 PMPPASS
Permit finaled
FIR14-00839 INSP-Sprinkler Rough-in8/11/20158/11/20158/11/2015 3:44:24 PMPDONE
Boise Fire Dept. witnessed the flowing water at the foam generators. Forrest France verified required pressure at foam generator.
BLD15-01247 FIRE-Final Inspection8/11/20158/11/20158/11/2015 3:42:13 PMPCANC
Overbooked. Rescheduled for tomorrow morning. Kelly Phone #: ###-####
FIR14-00928 INSP-Alarm Testing8/10/20158/11/20158/11/2015 2:53:17 PMADONE
Todays testing included all tamper switches except Fire Pump #1 intake (needs replaced) and all flow and pressure switches. The hose valve tampers/riser are labeled incorrectly. Also tested the fire pump interconnection to the FACP. Risers and fire pumps need labeling to match the FACP display. Need signal reports. Need plans resubmitted due to extensive changes which include using a 4009 NAC panel for releasing and a wireless dialer instead of phone lines and door mags that need releasing upon flow of water.
FIR15-00543 INSP-Final Inspection8/10/20158/11/20158/11/2015 2:09:17 PMPCANC
wrong permit called in.
FIR15-00143 INSP-Supply line flush8/11/20158/11/20158/11/2015 2:01:17 PMPPASS
Underground flush passed
FIR14-00746 INSP-Final Inspection8/11/20158/11/20158/11/2015 1:58:43 PMPPASS
permit finaled
FIR14-00746 INSP-Supply line flush8/11/20158/11/20158/11/2015 1:55:58 PMPPASS
Underground flush passed
BLD15-02359 FIRE-Final Inspection8/11/20158/11/20158/11/2015 11:34:12 AMPPASS
Life safety passed
BLD15-01248 FIRE-Final Inspection8/10/20158/11/20158/11/2015 10:39:14 AMAPASS
life safety passed
FIR15-00494 INSP-Final Inspection8/7/20158/11/20158/11/2015 10:37:11 AMAPASS
The walls for offices ws-1, ws-2 and ws-3 are low walls so the 15cd strobe was overspaced. The 15cd wall mount was changed to 110cd and EOL verifed. Lee will need as-builts. Permit finaled
BLD15-02287 FIRE-Final Inspection8/10/20158/11/20158/11/2015 10:34:38 AMAFAIL
Life safety will be ok to pass when the fire alarm and fire sprinkler corrections/permits have been made.
FIR15-00447 INSP-Final Inspection8/10/20158/11/20158/11/2015 7:04:18 AMAPASS
Permit finaled