Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00724 INSP-Alarm Testing8/11/20158/11/20158/11/2015 4:20:14 PMPPART
Continuation of fire alarm system testing, including test of two (2) PIVs, two (2) BFP devices - both valves, and a random etst of other fire sprinkler risers and sectional control valves. All tested OK.
Started FSD test of in-duct SDs to ensure shutdown of FSDs for the parking level, 1st floor kitchen and lobby and 2nd floor lobby areas. All tested OK, except for one unit in the garage that needs to be retested. More FSDs need to be tested on the upper floors including rooftop HVAV duct detectors.
FIR14-00813 INSP-Final Inspection8/7/20158/11/20158/11/2015 4:15:43 PMPPASS
6th floor kitchen Ansul system, including test of MP, Detection, gas/electric shutoff, balloon test, nozzle types/placement, etc. All passed OK. May need barrier between DF fryer and gas grill - not sure of distance between the two appliances.
FIR14-00328 INSP-Final Inspection8/7/20158/11/20158/11/2015 4:13:32 PMPPASS
Reinspection of Ansul FP system for the 1st floor kitchen lobby area. Previous test passed for balloon test, MP. gas/electric shut off, detection, etc. Just needed to confirm nozzle types and placement, which looked OK and a barrier between the DF fryer and the gas grill.