Inspections for the day of: Tuesday, August 12, 2003.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-02684 Electrical Rough-In8/11/20038/12/20038/12/2003 12:00:00 AMAPART
ernest ceiling cover; Phone #: ###-#### Internet Inspection Request from: Barbara Moore see print for area cor. posted for blind power source cords above dropped ceiling 8/12/2003 1:02:43 PM
ELE03-02376 Electrical Rough-In8/11/20038/12/20038/12/2003 12:00:00 AMAPART
mark; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie part u/g ok 8/12/2003 10:50:04 AM
ELE03-02386 Final8/11/20038/12/20038/12/2003 12:00:00 AMAPASS
john; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie see added p/s 8/12/2003 10:18:27 AM
ELE03-02387 Electrical Rough-In8/11/20038/12/20038/12/2003 12:00:00 AMANH
harold; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie notice posted called 8/12/2003 8:45:17 AM
ELE03-02414 Electrical Rough-In8/11/20038/12/20038/12/2003 12:00:00 AMANH
harold; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie notice posted called 8/12/2003 8:45:36 AM
ELE03-02440 Electrical Rough-In8/12/20038/12/20038/12/2003 12:00:00 AMAPASS
meet terry at 8:00 am ok 8/12/2003 8:18:08 AM
ELE03-02386 Permanent Service8/12/20038/12/20038/12/2003 12:00:00 AMAPASS
p /s u/g rec. ok
ELE03-02459 Electrical Rough-In8/12/20038/12/20038/12/2003 12:00:00 AMPFAIL
terry ###-#### cor. posted called nail plated and 11/4 inches needs approved wiremold box , and cablr to wiremold adapter, cables bends less than 5 times the diameter 8/12/2003 4:08:38 PM
ELE03-02408 Permanent Service8/12/20038/12/20038/12/2003 12:00:00 AMPPASS
p/s u/g new ok
ELE03-01370 Final8/12/20038/12/20038/12/2003 12:00:00 AMPPASS
owner secured contractor too take over work, see PM#ELE03-02459
ELE03-02408 Final8/12/20038/12/20038/12/2003 12:00:00 AMPPASS
Corrections performed.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchellok 8/12/2003 1:46:52 PM
ELE03-02394 Permanent Service8/6/20038/12/20038/12/2003 12:00:00 AMPFAIL
###-#### cor. posted called 250.92 bond nipple at p/s, 250.52(A)(1) grd water within 5 ft bond around di electrics bond hot and cold , 250.66 needs #4 copper for grd and bonds, 250.53 2 grd rods, 230.24 8ft over roof and support mast 8/12/2003 3:14:49 PM