ELE02-02684
| Electrical Rough-In | 8/11/2003 | 8/12/2003 | 8/12/2003 12:00:00 AM | A | PART |
|
|
ernest ceiling cover; Phone #: ###-#### Internet Inspection Request from: Barbara Moore see print for area cor. posted for blind power source cords above dropped ceiling 8/12/2003 1:02:43 PM
|
ELE03-02376
| Electrical Rough-In | 8/11/2003 | 8/12/2003 | 8/12/2003 12:00:00 AM | A | PART |
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie part u/g ok 8/12/2003 10:50:04 AM
|
ELE03-02386
| Final | 8/11/2003 | 8/12/2003 | 8/12/2003 12:00:00 AM | A | PASS |
|
|
john; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie see added p/s 8/12/2003 10:18:27 AM
|
ELE03-02387
| Electrical Rough-In | 8/11/2003 | 8/12/2003 | 8/12/2003 12:00:00 AM | A | NH |
|
|
harold; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie notice posted called 8/12/2003 8:45:17 AM
|
ELE03-02414
| Electrical Rough-In | 8/11/2003 | 8/12/2003 | 8/12/2003 12:00:00 AM | A | NH |
|
|
harold; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie notice posted called 8/12/2003 8:45:36 AM
|
ELE03-02440
| Electrical Rough-In | 8/12/2003 | 8/12/2003 | 8/12/2003 12:00:00 AM | A | PASS |
|
|
meet terry at 8:00 am ok 8/12/2003 8:18:08 AM
|
ELE03-02386
| Permanent Service | 8/12/2003 | 8/12/2003 | 8/12/2003 12:00:00 AM | A | PASS |
|
|
p /s u/g rec. ok
|
ELE03-02459
| Electrical Rough-In | 8/12/2003 | 8/12/2003 | 8/12/2003 12:00:00 AM | P | FAIL |
|
|
terry ###-#### cor. posted called nail plated and 11/4 inches needs approved wiremold box , and cablr to wiremold adapter, cables bends less than 5 times the diameter 8/12/2003 4:08:38 PM
|
ELE03-02408
| Permanent Service | 8/12/2003 | 8/12/2003 | 8/12/2003 12:00:00 AM | P | PASS |
|
|
p/s u/g new ok
|
ELE03-01370
| Final | 8/12/2003 | 8/12/2003 | 8/12/2003 12:00:00 AM | P | PASS |
|
|
owner secured contractor too take over work, see PM#ELE03-02459
|
ELE03-02408
| Final | 8/12/2003 | 8/12/2003 | 8/12/2003 12:00:00 AM | P | PASS |
|
|
Corrections performed.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchellok 8/12/2003 1:46:52 PM
|
ELE03-02394
| Permanent Service | 8/6/2003 | 8/12/2003 | 8/12/2003 12:00:00 AM | P | FAIL |
|
|
###-#### cor. posted called 250.92 bond nipple at p/s, 250.52(A)(1) grd water within 5 ft bond around di electrics bond hot and cold , 250.66 needs #4 copper for grd and bonds, 250.53 2 grd rods, 230.24 8ft over roof and support mast 8/12/2003 3:14:49 PM
|