BLD03-00439
| FIRE-Final Inspection | 8/11/2003 | 8/12/2003 | 8/12/2003 12:00:00 AM | A | PASS |
|
|
fire life safety finaled 8/13/2003 9:20:07 AM
|
BLD02-02623
| FIRE-Final Inspection | 8/11/2003 | 8/12/2003 | 8/12/2003 12:00:00 AM | A | FAIL |
|
|
scott; Phone #: ###-#### Remove thumbturn form main exit, provide approved hardware on the east exit, provide automatic shutdown for the hvac system per UMC 608, provide emergency light and exit sign in basement, breakroom in the basement is shown as a mech. room on the plans. This needs approve by the city 8/13/2003 11:20:35 AM
|
FIR03-00402
| INSP-Alarm Testing | 8/11/2003 | 8/12/2003 | 8/12/2003 12:00:00 AM | P | PASS |
|
|
fire alarm finaled 8/13/2003 9:33:22 AM
|
FIR03-00387
| INSP-Sprinkler Rough-in/Hydro | 8/11/2003 | 8/12/2003 | 8/12/2003 12:00:00 AM | P | FAIL |
|
|
armovers to pendants exceed 24"(nfpa 13 6-2.3.4), sprinkler piping is hung from other sprinkler piping(nfpa 13 6-2.1.3), too many pendants supplied from a single drop(notes #12, I, J), pendant head spacing in the file room exceeds spacing allowed per review note #9, provide retaining straps for all top beam clamps, the trapeze hanger is sized incorrectly for the armover support, provide inspection tag on riser, provide nfpa 25 or verification the owner has it per note #19 8/13/2003 10:54:47 AM
|
BLD03-01458
| FIRE-Final Inspection | 8/12/2003 | 8/12/2003 | 8/12/2003 12:00:00 AM | P | FAIL |
|
|
No approved plans on site and the hvac contractor that met me there did not know how the fire alarm panel operate so it could not be put in test 8/13/2003 9:32:14 AM
|
FIR03-00419
| INSP-Supply line flush | 8/12/2003 | 8/12/2003 | 8/12/2003 12:00:00 AM | P | PASS |
|
|
Underground supply is ok to cover 8/13/2003 9:32:43 AM
|