Inspections for the day of: Tuesday, August 12, 2003.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-00439 FIRE-Final Inspection8/11/20038/12/20038/12/2003 12:00:00 AMAPASS
fire life safety finaled 8/13/2003 9:20:07 AM
BLD02-02623 FIRE-Final Inspection8/11/20038/12/20038/12/2003 12:00:00 AMAFAIL
scott; Phone #: ###-#### Remove thumbturn form main exit, provide approved hardware on the east exit, provide automatic shutdown for the hvac system per UMC 608, provide emergency light and exit sign in basement, breakroom in the basement is shown as a mech. room on the plans. This needs approve by the city 8/13/2003 11:20:35 AM
FIR03-00402 INSP-Alarm Testing8/11/20038/12/20038/12/2003 12:00:00 AMPPASS
fire alarm finaled 8/13/2003 9:33:22 AM
FIR03-00387 INSP-Sprinkler Rough-in/Hydro8/11/20038/12/20038/12/2003 12:00:00 AMPFAIL
armovers to pendants exceed 24"(nfpa 13 6-2.3.4), sprinkler piping is hung from other sprinkler piping(nfpa 13 6-2.1.3), too many pendants supplied from a single drop(notes #12, I, J), pendant head spacing in the file room exceeds spacing allowed per review note #9, provide retaining straps for all top beam clamps, the trapeze hanger is sized incorrectly for the armover support, provide inspection tag on riser, provide nfpa 25 or verification the owner has it per note #19 8/13/2003 10:54:47 AM
BLD03-01458 FIRE-Final Inspection8/12/20038/12/20038/12/2003 12:00:00 AMPFAIL
No approved plans on site and the hvac contractor that met me there did not know how the fire alarm panel operate so it could not be put in test 8/13/2003 9:32:14 AM
FIR03-00419 INSP-Supply line flush8/12/20038/12/20038/12/2003 12:00:00 AMPPASS
Underground supply is ok to cover 8/13/2003 9:32:43 AM