FIR04-00499
| FIR-Aging Inspection | 8/12/2005 | 8/12/2005 | 8/16/2005 4:14:42 PM | | NR |
|
|
I spoke to Don and he will follow up
|
BLD05-00573
| FIRE-Final Inspection | 8/12/2005 | 8/12/2005 | 8/12/2005 4:31:43 PM | P | CANC |
|
|
Ran out of time for inspection
|
BLD05-00571
| FIRE-Final Inspection | 8/12/2005 | 8/12/2005 | 8/12/2005 4:31:23 PM | P | CANC |
|
|
Ran out of time for inspection
|
BLD05-00112
| FIRE-Final Inspection | 8/10/2005 | 8/12/2005 | 8/12/2005 4:16:11 PM | P | PASS |
|
|
Life safety finaled
|
FIR05-00461
| INSP-Sprinkler Rough-in/Hydro | 8/12/2005 | 8/12/2005 | 8/12/2005 4:15:52 PM | P | PASS |
|
|
Sprinkler rough-in passed
|
FIR05-00478
| INSP-Supply line flush | 8/12/2005 | 8/12/2005 | 8/12/2005 3:05:04 PM | P | PASS |
|
|
This inspection was not for a flush but for cover. Underground piping is ok for cover.
|
BLD05-01170
| FIRE-Final Inspection | 8/12/2005 | 8/12/2005 | 8/12/2005 3:01:39 PM | P | PASS |
|
|
Per the structural inspector all items have been corrected. Life safety finaled
|
FIR05-00155
| INSP-Sprinkler Rough-in/Hydro | 8/11/2005 | 8/12/2005 | 8/12/2005 2:55:24 PM | P | PASS |
|
|
Above ground hydro test passed. Contractor needs to provide test papers that have been filled out. I signed for the hydro test.
|
FIR05-00441
| INSP-Sprinkler Rough-in/Hydro | 8/11/2005 | 8/12/2005 | 8/12/2005 1:36:58 PM | P | PASS |
|
|
Underground supply piping is ok to cover
|
BLD05-01728
| FIRE-Final Inspection | 8/11/2005 | 8/12/2005 | 8/12/2005 1:14:48 PM | A | FAIL |
|
|
dominic; Phone #: ###-#### No city approved plans on site. Exit signs/ emergency lights, fire extinguishers and door hardware appear ok but need the plans to verify any other possible requirements.
|
BLD05-00261
| FIRE-Final Inspection | 8/11/2005 | 8/12/2005 | 8/12/2005 12:43:47 PM | A | FAIL |
|
|
Provide emergency lighting in main corridor and lobby. See sheet A2.01. Provide emergency lighting in each of the conference rooms. See sheet A2.01. Provide exit discharge lighting at the three exits. Must be listed for outdoor/cold weather. See review note #10. Provide additional text for the occupant load sign, "Dividers closed 66". Redduce storage height per note #13 (24"). Re-install hydraulic closers and provide gaskets on all doors in rated assemblies. Provide fire extinguisher for the new storage room. See note #3. Provide zoning and cfm information on the hvac system.
|
BLD03-01484
| FIRE-Final Inspection | 8/11/2005 | 8/12/2005 | 8/12/2005 10:52:11 AM | A | PASS |
|
|
rick ; Phone #: ###-#### Permit finaled. Per Rick the materials passed through the building and contained inside do not meet the definitions of hazardous materials per the msds sheets.
|
BLD05-00495
| FIRE-Final Inspection | 8/11/2005 | 8/12/2005 | 8/12/2005 10:07:54 AM | A | FAIL |
|
|
Jane, ###-#### - Remove thumbturns from the front and back doors. Keyed is ok if meeting the requirements of review notes #13 and #14. Turn hardware around on basement access door. Provide two fire extinguishers. One upstairs and one on the main level. See review note #12. Provide verification of the cfm rating for the main level hvac unit.
|
BLD03-02236
| FIRE-Final Inspection | 8/11/2005 | 8/12/2005 | 8/12/2005 9:22:19 AM | A | FAIL |
|
|
Need to repair the emergency lights in the stairwells and the exit discharge lighting. Provide NFPA 72 record of completion forms to the inspector as well.
|
FIR03-00737
| INSP-Final Inspection | 8/11/2005 | 8/12/2005 | 8/12/2005 9:21:08 AM | A | PASS |
|
|
fire alarm finaled
|
BLD05-01583
| FIRE-Final Inspection | 8/11/2005 | 8/12/2005 | 8/12/2005 8:44:08 AM | A | PASS |
|
|
Permit finaled. I could not find any IFC reference for fire alarm requirements for an existing "B" occupancy.
|
FIR05-00392
| INSP-Sprinkler Rough-in | 8/11/2005 | 8/12/2005 | 8/12/2005 8:04:54 AM | A | PASS |
|
|
rough-in passed. Final head spacing will be checked at the final since not all of the pendants had been snapped into the t-bar. Could not get into the riser room to verify annual inspection on the sprinkler system
|