Inspections for the day of: Friday, August 12, 2005.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00499 FIR-Aging Inspection8/12/20058/12/20058/16/2005 4:14:42 PM NR
I spoke to Don and he will follow up
BLD05-00573 FIRE-Final Inspection8/12/20058/12/20058/12/2005 4:31:43 PMPCANC
Ran out of time for inspection
BLD05-00571 FIRE-Final Inspection8/12/20058/12/20058/12/2005 4:31:23 PMPCANC
Ran out of time for inspection
BLD05-00112 FIRE-Final Inspection8/10/20058/12/20058/12/2005 4:16:11 PMPPASS
Life safety finaled
FIR05-00461 INSP-Sprinkler Rough-in/Hydro8/12/20058/12/20058/12/2005 4:15:52 PMPPASS
Sprinkler rough-in passed
FIR05-00478 INSP-Supply line flush8/12/20058/12/20058/12/2005 3:05:04 PMPPASS
This inspection was not for a flush but for cover. Underground piping is ok for cover.
BLD05-01170 FIRE-Final Inspection8/12/20058/12/20058/12/2005 3:01:39 PMPPASS
Per the structural inspector all items have been corrected. Life safety finaled
FIR05-00155 INSP-Sprinkler Rough-in/Hydro8/11/20058/12/20058/12/2005 2:55:24 PMPPASS
Above ground hydro test passed. Contractor needs to provide test papers that have been filled out. I signed for the hydro test.
FIR05-00441 INSP-Sprinkler Rough-in/Hydro8/11/20058/12/20058/12/2005 1:36:58 PMPPASS
Underground supply piping is ok to cover
BLD05-01728 FIRE-Final Inspection8/11/20058/12/20058/12/2005 1:14:48 PMAFAIL
dominic; Phone #: ###-#### No city approved plans on site. Exit signs/ emergency lights, fire extinguishers and door hardware appear ok but need the plans to verify any other possible requirements.
BLD05-00261 FIRE-Final Inspection8/11/20058/12/20058/12/2005 12:43:47 PMAFAIL
Provide emergency lighting in main corridor and lobby. See sheet A2.01. Provide emergency lighting in each of the conference rooms. See sheet A2.01. Provide exit discharge lighting at the three exits. Must be listed for outdoor/cold weather. See review note #10. Provide additional text for the occupant load sign, "Dividers closed 66".
Redduce storage height per note #13 (24"). Re-install hydraulic closers and provide gaskets on all doors in rated assemblies. Provide fire extinguisher for the new storage room. See note #3. Provide zoning and cfm information on the hvac system.
BLD03-01484 FIRE-Final Inspection8/11/20058/12/20058/12/2005 10:52:11 AMAPASS
rick ; Phone #: ###-####
Permit finaled. Per Rick the materials passed through the building and contained inside do not meet the definitions of hazardous materials per the msds sheets.
BLD05-00495 FIRE-Final Inspection8/11/20058/12/20058/12/2005 10:07:54 AMAFAIL
Jane, ###-#### -
Remove thumbturns from the front and back doors. Keyed is ok if meeting the requirements of review notes #13 and #14. Turn hardware around on basement access door. Provide two fire extinguishers. One upstairs and one on the main level. See review note #12. Provide verification of the cfm rating for the main level hvac unit.
BLD03-02236 FIRE-Final Inspection8/11/20058/12/20058/12/2005 9:22:19 AMAFAIL
Need to repair the emergency lights in the stairwells and the exit discharge lighting. Provide NFPA 72 record of completion forms to the inspector as well.
FIR03-00737 INSP-Final Inspection8/11/20058/12/20058/12/2005 9:21:08 AMAPASS
fire alarm finaled
BLD05-01583 FIRE-Final Inspection8/11/20058/12/20058/12/2005 8:44:08 AMAPASS
Permit finaled. I could not find any IFC reference for fire alarm requirements for an existing "B" occupancy.
FIR05-00392 INSP-Sprinkler Rough-in8/11/20058/12/20058/12/2005 8:04:54 AMAPASS
rough-in passed. Final head spacing will be checked at the final since not all of the pendants had been snapped into the t-bar. Could not get into the riser room to verify annual inspection on the sprinkler system