Inspections for the day of: Tuesday, August 12, 2008.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-03634 FIRE-Final Inspection8/11/20088/12/20088/18/2008 5:05:41 PMAFAIL
Failed per inspection comments 7/6/07.
BLD05-02070 FIRE-Final Inspection8/11/20088/12/20088/18/2008 5:00:45 PMAPART
Pending completion of building alarm and fire sprinkler work prior to permit final.
BLD06-00213 BLD-Final8/11/20088/12/20088/14/2008 9:57:47 AMADEFR
Barb----Dave this was given temp on 6-9-06 and I need to know if they did what was required to give them perm? See activity notes regarding inspection on 6-9-06. Please let me know...thanks Phone #: ###-#### sent to fire
BLD05-02144 FIRE-Final Inspection8/11/20088/12/20088/13/2008 4:52:09 PMAFAIL
Building renovation is not complete, still need project related shell fire sprinkler and alarm permit finals prior to permanent occupancy certificate.
BLD08-01649 FIRE-Final Inspection8/12/20088/12/20088/13/2008 8:05:44 AMPPASS
Life safety inspection passed.
BLD08-01648 FIRE-Final Inspection8/12/20088/12/20088/12/2008 3:30:22 PMPPASS
Fire life safety inspection passed.
BLD08-00480 FIRE-Final Inspection8/12/20088/12/20088/12/2008 3:29:11 PMPFAIL
Install approved hardware at the mechanical room door, provide "door to remain unlocked while building is occupied" signage at the main door, the existing vault door must be arranged to eliminate the potential for an occupant to be locked inside.
BLD08-00483 FIRE-Final Inspection8/12/20088/12/20088/12/2008 3:25:58 PMPFAIL
Missing signage at the main entry/exit door, provide a fire extinguisher within travel distances.
BLD08-00492 FIRE-Final Inspection8/12/20088/12/20088/12/2008 3:24:00 PMPFAIL
Provide approved hardware at the office door leading to the second exit, provide signage at the main entry/exit door or install hardware per review comments.
BLD08-01459 FIRE-Final Inspection8/12/20088/12/20088/12/2008 2:16:28 PMPPASS
Fire life safety inspection passed.
BLD07-03282 FIRE-Final Inspection8/11/20088/12/20088/12/2008 12:08:12 PMPFAIL
See items indicated on fire code review notes for project fire life safety requirements.
FIR08-00407 INSP-Final Inspection8/11/20088/12/20088/12/2008 12:03:17 PMAPASS
Fire alarm system modifications passed field testing, permit finaled.
FIR08-00405 INSP-Final Inspection8/11/20088/12/20088/12/2008 12:02:18 PMAPASS
Fire alarm permit finaled.
FIR08-00404 INSP-Final Inspection8/11/20088/12/20088/12/2008 12:01:35 PMAPASS
Fire alarm testing completed satisfactory, permit finaled.
BLD07-03283 FIRE-Final Inspection8/11/20088/12/20088/12/2008 12:00:35 PMANR
Project is not in condition for final fire life safety at this time.
BLD07-03281 FIRE-Final Inspection8/11/20088/12/20088/12/2008 11:59:23 AMANR
Discussed items with contractor needed for life safety final.
FIR08-00304 FIR-Aging Inspection8/12/20088/12/20088/12/2008 11:58:19 AM DEFR
Pending site inspection request for verification of work completion.
FIR08-00408 INSP-Final Inspection8/11/20088/12/20088/12/2008 11:56:39 AMAFAIL
See plans for location of one non-functional fire alarm notification device to be repaired.
FIR08-00480 INSP-Sprinkler Rough-in/Hydro8/11/20088/12/20088/12/2008 11:54:09 AMAFAIL
Overhead rough-in is not approved for cover at this time due to field changes in pipe routing/sizes, 6 added heads, one deleted head, an added kitchen storage room in an upper level including 2 heads not shown on drawings, relocated heads etc. Plans will need to be resubmitted for approval matching the field installation prior to okay for cover. Noted possible obstructions by soffits at three rooms in the basement which need to comply with NFPA 13D 8.2.5.4.3, head at the riser room needs relocated as discussed for exposed CPVC riser install, be aware of possible light fixture obstructions. UG supply flush completed okay.
FIR08-00309 INSP-Sprinkler Rough-in8/11/20088/12/20088/12/2008 11:43:21 AMAFAIL
See annotations on plan set for items in need of correction including spacing at pendent heads in the womens restroom, one painted head above the stairs 2nd floor, spacing at two heads adjacent to the elevator lobby, noted two heads at the first floor with excessive loading. Relocated heads at the kitchen area are okay for cover.