Inspections for the day of: Friday, August 12, 2011.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-01857 Temporary Service8/12/20118/12/20118/12/2011 2:55:21 PMPPASS
Darren Phone #: ###-#### t/s u/g n ok
ELE11-01853 Electrical Rough-In8/12/20118/12/20118/12/2011 1:48:16 PMPPASS
call for access Phone #: ###-#### >> Inspection requested via web by Aaron Decker ri ok
ELE11-01856 Electrical Rough-In8/12/20118/12/20118/12/2011 12:34:36 PMPFAIL
Wall inspection Phone #: ###-#### >> Inspection requested via web by Therrin Robertson called, left correction notice, NEC 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing member, 330.30(B) shall secure mc cable within 12" of box
ELE08-02423 Permanent Service8/12/20118/12/20118/12/2011 11:50:39 AMPPASS
ok to add meters as requested for units being completed, p/s ok'd earlier before job put on hold
MIS11-00198 ELE-Conference8/11/20118/12/20118/12/2011 10:14:26 AMADONE
JEREMY please call before going out Thanks Phone #: ###-#### met tenant, left correction notice, NEC 110.11 unless identified for use in the operating environment no equipment shall be located in damp or wet locations. NOTE: corrections shall be made within 12 days or further action will be taken, such as removal of power
ELE11-01781 Electrical Rough-In8/11/20118/12/20118/12/2011 8:59:26 AMAPASS
JIMMY Phone #: ###-#### ri ok