Inspections for the day of: Friday, August 12, 2011.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00308 INSP-Sprinkler Rough-in/Hydro8/12/20118/12/20118/12/2011 4:16:33 PMPPART
Hydrostatic testing passed for the new wet system manifolds and piping.
BLD11-01128 FIRE-Final Inspection8/11/20118/12/20118/12/2011 3:30:38 PMPPASS
Fire life safety completed satisfactory.
FIR11-00311 INSP-Final Inspection8/12/20118/12/20118/12/2011 3:29:42 PMPPASS
Scope of work completed. Correction item verified. Fire sprinkler permit finaled.
FIR11-00333 INSP-Final Inspection8/12/20118/12/20118/12/2011 3:28:08 PMPPASS
Fire alarm testing passed. Permit final approved.
BLD10-02822 FIRE-Final Inspection8/12/20118/12/20118/12/2011 3:27:19 PMAPASS
Life safety passed. Fire extinguisher has been installed and tagged per R. Criner. Signature card not on site.
FIR11-00308 INSP-Sprinkler Rough-in/Hydro8/12/20118/12/20118/12/2011 3:24:24 PMAPART
Overhead rough-in for the new dry system completed. Noted items include; replace three BB1 attic heads due to modified deflector/frame orientation, one upright head at the NE dormer is obstructed by truss webs, one EQ brace secured while on site.
FIR11-00355 INSP-Sprinkler Rough-in/Hydro8/10/20118/12/20118/12/2011 3:21:07 PMAPART
Inspection completed for portions of the 1st and 2nd floors remodeled and new additions as marked on stamped plan set. Noted items include; 1st floor- missing 4 seismic braces, overspaced uprights at room 101 and 109, 2nd floor- pipe sizing at room 200 does not match plan, need to sheetrock concealed space or provide sprinkler protection, provide clearance at the floor for the 2" dry feed to the wheelchair ramp. Okay to cover new exterior canopy and ceiling above the ramp.