Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-00062 ELE-Aging Inspection8/12/20118/12/20118/12/2011 3:53:41 PM DONE
still under construction
ELE11-01859 Rough-In Permanent Service8/12/20118/12/20118/12/2011 3:45:49 PMPPASS
Electrician is Jon. Phone #: ###-#### >> Inspection requested via web by joel smith p/s u/g rec ok for 14 days service panel does not meet working clearances do to hot tub installation. Hot tub or service panel shall be relocated within 14 days
ELE11-01709 Final8/12/20118/12/20118/12/2011 2:11:03 PMPNR
At end of day. Jeff ###-#### Thanks, Andrea. Phone #: ###-#### x0000 >> Inspection requested via web by Andrea Creek
ELE11-01858 Temporary Service8/12/20118/12/20118/12/2011 2:09:48 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson t/s u/g meter pac
ELE11-01709 Permanent Service8/12/20118/12/20118/12/2011 2:03:12 PMPPASS
Service change occupied home, need in "early" pm please. Call Jeff ###-#### for coordination. Thanks, Andrea. Phone #: ###-#### x0000 >> Inspection requested via web by Andrea Creek p/s u/g rec ok
ELE11-01320 Final8/12/20118/12/20118/12/2011 12:55:11 PMPPASS
Please give me half an hour notice to insure access is ready anytime Phone #: ###-#### >> Inspection requested via web by Shaun Kirkman final ok
ELE11-01855 Final8/12/20118/12/20118/12/2011 12:30:54 PMPPASS
final ok
ELE11-01855 Electrical Rough-In8/12/20118/12/20118/12/2011 12:26:01 PMPPASS
Approval to cover trench Phone #: ###-#### >> Inspection requested via web by Andy Derrick rough-in ok cover trench
GCE11-00085 GCE-Permanent Service8/11/20118/12/20118/12/2011 10:08:28 AMAPASS
Perm ServiceDebbie @ ###-####Call in advance p/s u/g rec ok call back in for final inspection when ready.
ELE11-01852 Final8/12/20118/12/20118/12/2011 9:45:38 AMPPASS
final ok add GFCI receptacle in garage
ELE11-01852 Electrical Rough-In8/12/20118/12/20118/12/2011 9:44:46 AMAPASS
Phone #: ###-#### >> Inspection requested via web by PAT MILLER rough-in ok
ELE11-01777 Electrical Rough-In8/11/20118/12/20118/12/2011 9:22:34 AMAFAIL
Rich Park Phone #: ###-#### sub panel not service rated,seperate neutrals and ground wires,provide main breaker, service junction box needs to be grounded
ELE11-01642 Electrical Rough-In7/27/20118/12/20118/12/2011 8:51:40 AMAPASS
Eric ###-#### rough-in ok cover