ELE13-02133
| Rough-In Permanent Service | 8/9/2013 | 8/12/2013 | 8/12/2013 2:21:45 PM | P | NR |
|
|
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn met contractor, looked at some activities, will recall
|
ELE13-02144
| Temporary Service | 8/12/2013 | 8/12/2013 | 8/12/2013 1:28:42 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE13-02145
| Temporary Service | 8/12/2013 | 8/12/2013 | 8/12/2013 1:04:43 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE13-01999
| Electrical Rough-In | 8/12/2013 | 8/12/2013 | 8/12/2013 12:22:36 PM | P | FAIL |
|
|
martin Phone #: ###-#### called, no answer, left correction notice, shall staple nm within 8" of box, shall provide nailplates, shall provide 1 1/4" protection of nm cable on studs, shall staple staple nm cable out of panel
|
ELE13-02143
| Temporary Service | 8/11/2013 | 8/12/2013 | 8/12/2013 10:33:48 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey called, shall provide working clearance per NEC 110.26(A)(2)
|
ELE12-03075
| Final | 8/11/2013 | 8/12/2013 | 8/12/2013 10:15:13 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Darrin Bybee called, shall add receptacle downstairs bedroom entry per NEC 210.52, shall label panels per NEC 408, pool lights shall be gfci protected, shall provide correct breakers in pool area panel
|
ELE13-02139
| Permanent Service | 8/9/2013 | 8/12/2013 | 8/12/2013 8:54:40 AM | A | PASS |
|
|
Contact: Garrett Collins Phone #: ###-#### >> Inspection requested via web by Deb Gooden p/s u/g n ok
|
ELE13-01531
| Final | 8/11/2013 | 8/12/2013 | 8/12/2013 8:36:51 AM | A | PASS |
|
|
garage code 9045 Phone #: ###-#### >> Inspection requested via web by Neal Rumsey ok final
|