Inspections for the day of: Monday, August 12, 2013.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD12-00687 FIRE-Final Inspection8/12/20138/12/20138/13/2013 9:25:14 AMPPASS
life safety passed
BLD12-00688 FIRE-Final Inspection8/12/20138/12/20138/13/2013 9:24:35 AMPPASS
life safety passed
BLD12-00686 FIRE-Final Inspection8/12/20138/12/20138/13/2013 9:24:05 AMPPASS
life safety passed
BLD12-00685 FIRE-Final Inspection8/12/20138/12/20138/13/2013 9:23:26 AMPPASS
life safety passed
FIR13-00343 INSP-Sprinkler Rough-in8/12/20138/12/20138/12/2013 2:35:48 PMPPASS
Underground is ok to cover.
BLD13-01575 FIRE-Final Inspection8/9/20138/12/20138/12/2013 2:33:15 PMAPASS
life safety passed
FIR13-00204 INSP-Sprinkler Rough-in/Hydro8/9/20138/12/20138/12/2013 2:32:41 PMAFAIL
Hydro test failed due to a visible drop in pressure at the guage. Also sprinkler coverage has not been installed under an overhead door. This work will need to be done prior to a hydro test.
BLD13-02178 FIRE-Final Inspection8/9/20138/12/20138/12/2013 10:27:43 AMAFAIL
Based on the limited information provided on the plans, at this time I'm going to require a fire extinguisher mounted and tagged as discussed and a sticker at the main exit. This is for the office area only.
FIR13-00113 INSP-Final Inspection8/9/20138/12/20138/12/2013 10:24:25 AMAFAIL
Provide knox box, provide map at facp, provide signage on FACP door, provide dedicated/locked out circuit for the FACP, provide listed enclosures for the duct smoke detectors and then test them, provide verification the kitchen hvac unit does not require a detector, provide correct zone descriptions at central station and retest everything