Inspections for the day of: Tuesday, August 12, 2014.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
GCE14-00115 GCE-Rough-In Permanent Service8/12/20148/12/20148/12/2014 2:08:51 PMPFAIL
Daniel ###-#### 250.8(A)(1)- grounded electrical system connection to grounding electrode system loose on both ground rods.
300.4- NM cable shall be protectedfrom physical damage when ran through bored holes that do not maintain 1 1/4" from framing surface
ELE14-01609 Final8/12/20148/12/20148/12/2014 1:50:36 PMPPASS
2474 is garage code Phone #: ###-#### Inspection requested via web by TOM BICANDI Final ok
GCE14-00116 GCE-Permanent Service8/12/20148/12/20148/12/2014 1:16:09 PMPFAIL
Daniel ###-#### 250.4(A)(1)- Grounded electrical systems shall be connected to earth in an approved manner. Ground electorde systym shall be provided and connected to service.
ELE14-02203 Electrical Rough-In8/11/20148/12/20148/12/2014 10:13:06 AMAPASS
pool bonding lights-cover-track Phone #: ###-#### Inspection requested via web by Kevin Koomler 5 stubs on each long side of pool. Rough in ok cover
ELE14-02202 Final8/11/20148/12/20148/12/2014 10:11:07 AMAPASS
Phone #: ###-#### Insp in ok coverection requested via web by Mike Okamura 5 stubs on each long side of pool. Rough in ok cover
ELE14-02202 Electrical Rough-In8/12/20148/12/20148/12/2014 9:31:27 AMPPASS
Phone #: ###-#### Inspection requested via web by Mike Okamura AC rough in ok
ELE14-01573 Final8/12/20148/12/20148/12/2014 9:02:22 AMAPASS
ANY ? CALL TOM CODE 7052 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok