Inspections for the day of: Wednesday, August 12, 2015.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-01568 ELE-Aging Inspection8/12/20158/12/20158/13/2015 7:25:04 AM CANC
Too busy
ELE15-02088 Final8/12/20158/12/20158/12/2015 2:17:45 PMPFAIL
Side gate open, back garage door unlocked. No pets. Not wiring greenhouse only new sub panel with 120v. Outlet. Thanks Mike Phone #: ###-#### Inspection requested via web by michael hunt 406.12- All 15 or 20 amp 120 volt receptacle outlets installed in or on a residence shall be tamper resistant type
ELE15-02422 Rough-In Permanent Service8/11/20158/12/20158/12/2015 1:54:27 PMPPASS
Phone #: ###-#### Inspection requested via web by Tracy Robertson Rough in ok cover p/s u/g n ok
ELE15-02432 Final8/12/20158/12/20158/12/2015 1:15:55 PMPPASS
Inspection requested via web by Jarod Murray Final ok
ELE15-00414 Final8/11/20158/12/20158/12/2015 12:10:12 PMAFAIL
Key in lock box in down stairs common area code 193 Phone #: ###-#### Inspection requested via web by cal crosby 210.8- Unable to test GFCI in 201 and 103, receptacles dead. 404.9- Cover shall be installed to switch in 201. Access not available to living room with appliances stacked in it. Appliances not set at the time of inspection, not able to check cord installation.
ELE15-02519 Electrical Rough-In8/11/20158/12/20158/12/2015 11:04:02 AMAPASS
Phone #: ###-#### Inspection requested via web by Mike Okamura Underground rough in ok cover
ELE15-02259 Electrical Rough-In8/11/20158/12/20158/12/2015 10:32:59 AMAPASS
please contact Cory with any questions - ###-####
thanks, Phone #: ###-#### Inspection requested via web by Cyndi Dale Service completed but did not request service inspection and available fault current not posted. 22k rated main. Called and left message about service with contact. Repair shop just behind sales office rough in ok cover
ELE15-02501 Final8/10/20158/12/20158/12/2015 9:29:29 AMAPASS
Install and wire new dedicated circuit from the MCC center to the new finish roller in the center of the south wall. This work area is located in the truss plant at the northwest corner of the property. Phone #: ###-#### Inspection requested via web by Dan Mitchell Final ok
ELE15-02501 Electrical Rough-In8/10/20158/12/20158/12/2015 9:28:47 AMAPASS
Install and wire new dedicated circuit from the MCC center to the new finish roller in the center of the south wall. This work area is located in the truss plant at the northwest corner of the property. Phone #: ###-#### Inspection requested via web by Dan Mitchell Rough in ok
ELE15-02505 Rough-In Permanent Service8/11/20158/12/20158/12/2015 8:44:37 AMAPASS
Phone #: ###-#### Inspection requested via web by Rowdy Monroe Rough in ok cover p/s u/g n ok
ELE15-02383 Electrical Rough-In8/10/20158/12/20158/12/2015 7:52:51 AMACANC
Call when headed my way. ###-####. Thanks Richard Phone #: ###-#### Inspection requested via web by Richard Corn Needed PM inspection