Inspections for the day of: Wednesday, August 12, 2015.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-01555 ELE-Aging Inspection8/12/20158/12/20158/12/2015 2:41:08 PM DONE
Kathy will call in for final
ELE15-02522 Final8/12/20158/12/20158/12/2015 2:35:36 PMPFAIL
This is located in Suite #100 you need to either call Jeff at ###-#### before to meet you there or go to Suite 300 and they will have a key for entrance. Thank you Phone #: ###-#### Inspection requested via web by Celinda Winters please call for "perm. service" for power. 110.16-arc flash label, 110.24- available fault current on main disconnect
ELE14-03246 Electrical Rough-In8/12/20158/12/20158/12/2015 2:03:20 PMPPASS
Levi. Pods on towers 3 ; 4 levels 5 ; 4 final. Phone #: ###-#### Inspection requested via web by Sean DeLacy final ok rms 506 thru 509
ELE15-01348 Electrical Rough-In8/12/20158/12/20158/12/2015 1:06:00 PMPPASS
Slab inspection: HQ Lvl4, Zone 3 Phone #: ###-#### Inspection requested via web by Tom Betty r/i ok level 4 zone 3 slab on deck
ELE15-01314 Final8/11/20158/12/20158/12/2015 11:03:44 AMAPASS
Lynn Phone #: ###-#### final ok still need arc flash stickers on upst. loadcenters 110.16 and available fault current on main outside with date 110.24.
ELE15-02511 Final8/11/20158/12/20158/12/2015 10:17:31 AMAPASS
If you have questions, please call Calvin ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan final ok
ELE15-02511 Electrical Rough-In8/11/20158/12/20158/12/2015 10:08:38 AMAPASS
If you have questions, please call Calvin ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan r/i ok
ELE15-02517 Electrical Rough-In8/11/20158/12/20158/12/2015 9:43:58 AMANR
call ###-#### for access Phone #: ###-#### Inspection requested via web by David Nelson discussed electric requirements in "birthing rooms" considered "wet procedure location" in NEC 517.18 shall have redundant ground system. not ready for r/i at this time.
GCE15-00127 GCE-Temporary Service8/11/20158/12/20158/12/2015 8:34:22 AMAPASS
###-#### t/s u/g n ok
ELE15-01521 Final8/11/20158/12/20158/11/2015 10:01:07 AMPCANC
Any questions please let me know, thx, TW. Phone #: ###-#### >> Inspection requested via web by Stephen Kren Inspection cancelled from web by: Stephen Kren
ELE15-01759 Final8/11/20158/12/20158/11/2015 10:00:24 AMPCANC
Any questions please let me know, thx, TW. Phone #: ###-#### >> Inspection requested via web by Stephen Kren Inspection cancelled from web by: Stephen Kren
ELE15-01671 Final8/11/20158/12/20158/11/2015 9:59:37 AMPCANC
Any questions please let me know, thx, TW. Phone #: ###-#### >> Inspection requested via web by Stephen Kren Inspection cancelled from web by: Stephen Kren