FIR14-00928
| INSP-Final Inspection | 8/12/2015 | 8/12/2015 | 8/12/2015 3:28:14 PM | P | FAIL |
|
|
Was only able to test the tamper for fire pump #1 suction valve today due to foam dump. Overhead doors and duct smoke detector not ready
|
FIR14-00839
| INSP-Sprinkler Rough-in | 8/12/2015 | 8/12/2015 | 8/12/2015 3:25:41 PM | P | PASS |
|
|
Todays inspection was for flow verification of the foam system. This verification failed. See the plan reviewer attached notes on the specificsof what was witnessed
______________________________________
Below add by Plan Reviewer TRF
Based on the following the foam test PASSED.
NFPA 409 6.1.1 (3)
NFPA 409 6.2.5.3 (withing 5' in 3 minutes)
NFPA 409 6.2.5.5.1 (local application, NFPA 11)
NFPA 11 6.13.3.3.1 (2 ft within 2 min)
The requiment of 2' of foam was met in 1:50 seconds.
|
FIR15-00031
| INSP-Final Inspection | 8/11/2015 | 8/12/2015 | 8/12/2015 3:22:18 PM | P | CANC |
|
|
Overbooked. To be rescheduled
|
BLD14-02241
| FIRE-Final Inspection | 8/12/2015 | 8/12/2015 | 8/12/2015 3:21:20 PM | P | CANC |
|
|
Overbooked. To be rescheduled for tomorrow
|
FIR15-00215
| INSP-Sprinkler Rough-in/Hydro | 8/12/2015 | 8/12/2015 | 8/12/2015 11:30:45 AM | P | PASS |
|
|
Overhead hydro test passed
|
FIR15-00468
| INSP-Final Inspection | 8/11/2015 | 8/12/2015 | 8/12/2015 11:30:03 AM | A | CANC |
|
|
Gas not set up yet for hvac unit
|
FIR15-00219
| INSP-Sprinkler Rough-in/Hydro | 8/12/2015 | 8/12/2015 | 8/12/2015 11:29:26 AM | P | PASS |
|
|
Overhead hydro test passed
|
FIR15-00216
| INSP-Sprinkler Rough-in/Hydro | 8/12/2015 | 8/12/2015 | 8/12/2015 11:26:24 AM | P | PASS |
|
|
overhead hydro test passed
|
FIR15-00217
| INSP-Sprinkler Rough-in/Hydro | 8/12/2015 | 8/12/2015 | 8/12/2015 11:24:53 AM | P | PASS |
|
|
overhead hydro test passed
|
FIR15-00218
| INSP-Sprinkler Rough-in/Hydro | 8/12/2015 | 8/12/2015 | 8/12/2015 11:23:58 AM | P | PASS |
|
|
Overhead hydro test passed
|
FIR15-00220
| INSP-Sprinkler Rough-in/Hydro | 8/12/2015 | 8/12/2015 | 8/12/2015 11:22:40 AM | P | PASS |
|
|
Overhead hydro test passed
|
FIR15-00221
| INSP-Sprinkler Rough-in/Hydro | 8/12/2015 | 8/12/2015 | 8/12/2015 11:21:51 AM | P | PASS |
|
|
Overhead hydro test passed
|
FIR15-00222
| INSP-Sprinkler Rough-in/Hydro | 8/12/2015 | 8/12/2015 | 8/12/2015 10:22:17 AM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR15-00223
| INSP-Sprinkler Rough-in/Hydro | 8/12/2015 | 8/12/2015 | 8/12/2015 10:21:43 AM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD15-01198
| FIRE-Final Inspection | 8/11/2015 | 8/12/2015 | 8/12/2015 10:09:10 AM | A | FAIL |
|
|
Remove deadbolt from rear exit door, repair all exit signs/emergency lights, provide sticker at the main exit and provide annual inspection tag for the fire extinguishers.
|
FIR15-00503
| INSP-Sprinkler Rough-in | 8/11/2015 | 8/12/2015 | 8/12/2015 8:53:06 AM | A | PASS |
|
|
Underground supply stub out only ok to cover.
|
BLD15-01181
| FIRE-Final Inspection | 8/11/2015 | 8/12/2015 | 8/12/2015 8:24:28 AM | A | PASS |
|
|
Life safety passed
|