FIR14-00928 INSP-Final Inspection8/12/20158/12/20158/12/2015 3:28:14 PMPFAIL
Was only able to test the tamper for fire pump #1 suction valve today due to foam dump. Overhead doors and duct smoke detector not ready
FIR14-00839 INSP-Sprinkler Rough-in8/12/20158/12/20158/12/2015 3:25:41 PMPPASS
Todays inspection was for flow verification of the foam system. This verification failed. See the plan reviewer attached notes on the specificsof what was witnessed

______________________________________
Below add by Plan Reviewer TRF

Based on the following the foam test PASSED.

NFPA 409 6.1.1 (3)
NFPA 409 6.2.5.3 (withing 5' in 3 minutes)
NFPA 409 6.2.5.5.1 (local application, NFPA 11)
NFPA 11 6.13.3.3.1 (2 ft within 2 min)
The requiment of 2' of foam was met in 1:50 seconds.



FIR15-00031 INSP-Final Inspection8/11/20158/12/20158/12/2015 3:22:18 PMPCANC
Overbooked. To be rescheduled
BLD14-02241 FIRE-Final Inspection8/12/20158/12/20158/12/2015 3:21:20 PMPCANC
Overbooked. To be rescheduled for tomorrow
FIR15-00215 INSP-Sprinkler Rough-in/Hydro8/12/20158/12/20158/12/2015 11:30:45 AMPPASS
Overhead hydro test passed
FIR15-00468 INSP-Final Inspection8/11/20158/12/20158/12/2015 11:30:03 AMACANC
Gas not set up yet for hvac unit
FIR15-00219 INSP-Sprinkler Rough-in/Hydro8/12/20158/12/20158/12/2015 11:29:26 AMPPASS
Overhead hydro test passed
FIR15-00216 INSP-Sprinkler Rough-in/Hydro8/12/20158/12/20158/12/2015 11:26:24 AMPPASS
overhead hydro test passed
FIR15-00217 INSP-Sprinkler Rough-in/Hydro8/12/20158/12/20158/12/2015 11:24:53 AMPPASS
overhead hydro test passed
FIR15-00218 INSP-Sprinkler Rough-in/Hydro8/12/20158/12/20158/12/2015 11:23:58 AMPPASS
Overhead hydro test passed
FIR15-00220 INSP-Sprinkler Rough-in/Hydro8/12/20158/12/20158/12/2015 11:22:40 AMPPASS
Overhead hydro test passed
FIR15-00221 INSP-Sprinkler Rough-in/Hydro8/12/20158/12/20158/12/2015 11:21:51 AMPPASS
Overhead hydro test passed
FIR15-00222 INSP-Sprinkler Rough-in/Hydro8/12/20158/12/20158/12/2015 10:22:17 AMPCANC
Phone #: ###-#### Inspection requested via web by Sam Ball
FIR15-00223 INSP-Sprinkler Rough-in/Hydro8/12/20158/12/20158/12/2015 10:21:43 AMPCANC
Phone #: ###-#### Inspection requested via web by Sam Ball
BLD15-01198 FIRE-Final Inspection8/11/20158/12/20158/12/2015 10:09:10 AMAFAIL
Remove deadbolt from rear exit door, repair all exit signs/emergency lights, provide sticker at the main exit and provide annual inspection tag for the fire extinguishers.
FIR15-00503 INSP-Sprinkler Rough-in8/11/20158/12/20158/12/2015 8:53:06 AMAPASS
Underground supply stub out only ok to cover.
BLD15-01181 FIRE-Final Inspection8/11/20158/12/20158/12/2015 8:24:28 AMAPASS
Life safety passed