Inspections for the day of: Friday, August 12, 2016.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-00908 ELE-Aging Inspection8/12/20168/12/20168/12/2016 2:54:03 PM PASS
Waiting on owner
ELE13-00039 ELE-Aging Inspection8/12/20168/12/20168/12/2016 2:53:09 PM PASS
Waiting on contractor
ELE12-02853 ELE-Aging Inspection8/12/20168/12/20168/12/2016 2:52:31 PM PASS
Waiting on contractor
ELE15-01348 Rough-In Permanent Service8/12/20168/12/20168/12/2016 2:51:53 PMPPASS
Annex HV XFMR 5, 1600 amp MAIN MSSE, 1600 amp Buss Duct MSSE,Grounding Electrode System, Main Bonding Jumper. Want to Energize , Doors and Panic Hwd Annex Phone #: ###-#### Inspection requested via web by Tom Betty
SWHQ stair #2 levels6-9, annex core walls level 5 Phone #: ###-#### Inspection requested via web by Brandon Robinson
Wall rough in as noted ok cover. Annex service ok to energize for temp 200 amp power only. Door issues with electical room.
ELE15-01348 Electrical Rough-In8/12/20168/12/20168/12/2016 2:51:14 PMPFAIL
Annex HV XFMR 5, 1600 amp MAIN MSSE, 1600 amp Buss Duct MSSE,Grounding Electrode System, Main Bonding Jumper. Want to Energize , Doors and Panic Hwd Annex Phone #: ###-#### Inspection requested via web by Tom Betty
NEC 110.26(C)(2)- For electrical equipment rated 1200 amps or more and 6 ft wide or more doors for egress shall be at each end of work space. Doors shall remain.
NEC 110.26(C)(3)- Doors located within 25' of electrical gear rated 800 amps or more shall have panic hardware. Doors shall open out in direcion of egress.
If correction not complete by 8-19-16 step will be taken to disconnect power from electrical gear in rooms OBG 121 and 122.
ELE16-01838 Electrical Rough-In8/12/20168/12/20168/12/2016 2:20:23 PMPCANC
SWHQ stair #2 levels6-9, annex core walls level 5 Phone #: ###-#### Inspection requested via web by Brandon Robinson
Wrong permit requested needed core and shell permit
ELE16-01477 Final8/12/20168/12/20168/12/2016 1:18:05 PMPPART
Partial final in Deli area only call cody for questions Phone #: ###-#### Inspection requested via web by Shane Lott
Deli temp occupy OK
ELE16-02623 Electrical Rough-In8/11/20168/12/20168/12/2016 11:45:05 AMAPASS
Uffer ground inspection. Contact Craig Timmons Phone #: ###-#### Inspection requested via web by Cathy Duchek
Concrete encase electrode rough in ok cover.
ELE16-02410 Final8/11/20168/12/20168/12/2016 11:03:35 AMAPASS
Phone #: ###-#### Inspection requested via web by Dean Gernaat
Final ok
ELE15-01617 Electrical Rough-In8/11/20168/12/20168/12/2016 10:32:00 AMANH
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Called contact no answer left message. Must Recall
ELE15-02740 Final8/11/20168/12/20168/12/2016 10:16:21 AMAPART
Seth ###-#### Check switches have been removed.
Switches romoved. Temp occupancy OK
ELE16-02578 Conference8/12/20168/12/20168/12/2016 9:50:59 AMPDONE
Discussed underground, expansion joint, garage receptacles tamper, GFCI protection and all electrical above 18", and required work space for sub-panel.
ELE16-01477 Final8/11/20168/12/20168/12/2016 9:11:45 AMAFAIL
PARTIAL FINAL ** for DELI area only** in the morning if possible
Call cody for questions ###-#### Phone #: ###-#### Inspection requested via web by Shane Lott Building permit lists deli area as meat and seafood area so all of area shall comply with 210.8- all 120 volt receptacle outlets shall have GFCI protection. Back area and north display case receptacles.