Inspections for the day of: Friday, August 12, 2016.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-02453 Final8/12/20168/12/20168/12/2016 1:51:43 PMPPASS
We Thought This Was Finaled Out. But Its Done . thanks Dave Phone #: ###-#### Inspection requested via web by jason shifflett
service change final ok
ELE15-02698 Final8/12/20168/12/20168/12/2016 1:36:34 PMPPASS
Dana Phone #: ###-####
sign final ok
ELE16-02603 Final8/12/20168/12/20168/12/2016 1:28:08 PMPPASS
Inspection requested via web by Jesse Fuentes
back patio final ok
ELE16-02279 Final8/12/20168/12/20168/12/2016 12:40:01 PMPPASS
This sign is not new - Move only. Phone #: ###-#### Inspection requested via web by Dana Vance
sign final ok
ELE16-02493 Electrical Rough-In8/11/20168/12/20168/12/2016 11:15:30 AMAPASS
kitchen ceiling grid, around 11am if possible Phone #: ###-#### Inspection requested via web by Lee VanSchoiack
kitchen area ceilings ok cover
ELE16-01664 Final8/11/20168/12/20168/12/2016 10:49:19 AMAPASS
Can move to PM if you need. Phone #: ###-#### Inspection requested via web by Heath Thomas
final ok
ELE16-02442 Permanent Service8/11/20168/12/20168/12/2016 10:15:26 AMAFAIL
Service inspection for Modular classroom. Contact is Bill Stokes. Phone #: ###-#### Inspection requested via web by Richard Montgomery
110.24 available fault current shall be posted
ELE16-02444 Permanent Service8/11/20168/12/20168/12/2016 10:14:50 AMAFAIL
Service inspection for Modular classroom. Contact is Bill Stokes. Phone #: ###-#### Inspection requested via web by Richard Montgomery
110.24 Available fault current shall be posted
ELE16-02445 Permanent Service8/11/20168/12/20168/12/2016 10:14:04 AMAFAIL
Service inspection for Modular classroom. Contact is Bill Stokes. Phone #: ###-#### Inspection requested via web by Richard Montgomery
110.24 available fault current shall be posted
ELE16-02446 Permanent Service8/11/20168/12/20168/12/2016 10:13:35 AMAFAIL
Service inspection for Modular classroom. Contact is Bill Stokes. Phone #: ###-#### Inspection requested via web by Richard Montgomery
110.24 available fault current shall be posted
ELE16-01974 Final8/10/20168/12/20168/12/2016 9:25:38 AMAPASS
Phone #: ###-#### Inspection requested via web by Justin Frates final for service change ok
ELE16-01213 Final8/11/20168/12/20168/12/2016 9:25:06 AMAFAIL
Gil Phone #: ###-####
406.4 outside receptacles shall be weather resistant type
210.8 all 120v receptacles shall have GFCI protection and be readily accessible
352.30 PVC shall be secured wihin 36" of a box
ELE13-00910 ELE-Aging Inspection8/12/20168/12/20168/12/2016 8:04:35 AM CANC
too busy