Inspections for the day of: Wednesday, August 12, 2020.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-00466 Final8/11/20208/12/20208/12/2020 3:29:01 PMPPASS
Mitch */Virtual Inspection Requested.*/ Phone #: ###-#### Owner elderly, does not want exposure to others Confirmed labelling verbally. Final ok
ELE19-00601 Electrical Rough-In8/12/20208/12/20208/12/2020 3:03:44 PMPPART
Cover for 4th/5th elevator lobbies. Tyson is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Level 5 elevator lobby access located too far from damper disconnecting means, can installed in access framed. Level 4 elevator lobby rough in ok cover,
ELE19-04799 Conference8/12/20208/12/20208/12/2020 2:40:52 PMPPASS
Discussed grounding requirements of each service. Bonding of grounded conductor completed in vault. Parallel grounded conductors and grounding conductor installed from vault to each service disconnecting means . As per 250.24 (A),(B), and (C) stating a main bonding jumper shall be installed at each service disconnecting means connecting the grounded conductor to the enclosure and equipment grounds. This requirement will create a parallel path between the grounded conductors and the grounding conductor from vault to each service. To comply with 250.24 the equipment ground from the vault to each service will need to be removed, or abandoned and as permitted by 250.142 non-current carrying metal of service enclosure will bond thru the grounded conductors.
ELE20-01794 Final8/11/20208/12/20208/12/2020 2:19:30 PMPPART
partial final for upstairs conference rooms and training room and on 1st floor work lab and downstairs bathroom Tyson is site contact ###-#### Phone #: ###-#### Inspection requested via web by Shane Lott 1 Receptacle in lab requires GFCI, with in 6' of sink as per 210.8(B). Areas noted TCO ok
ELE20-02806 Permanent Service8/12/20208/12/20208/12/2020 1:43:47 PMPPASS
The disconnect on the NW corner of Parkcenter Blvd ; River Run Dr. is ready for inspection. Please call Joe with any questions. ###-#### Phone #: ###-#### Inspection requested via web by Joe McLean
Ohm test results will be provided. p/s u/g n ok
MIS20-00251 ELE-Conference8/11/20208/12/20208/12/2020 1:26:33 PMADONE
remodelling without permits Phone #: ###-#### Appears to be a kitchen cabinet upgrade, some windows and carpet has been removed from what is in dumpster. No answer at door. Left correction notice asking owner to call to discuss.
ELE20-02817 Final8/11/20208/12/20208/12/2020 10:52:30 AMAFAIL
Call Andrew with any questions. Thank you. Phone #: ###-#### Inspection requested via web by Kelly Tarter 250.24- Main bonding jumper shall be installed to connect the grounded conductor to the enclosure and the equipment grounding conductors of the service disconnecting means.
ELE20-02748 Electrical Rough-In8/11/20208/12/20208/12/2020 10:05:50 AMAPASS
Phone #: ###-#### Inspection requested via web by Therrin Robertson Rough in ok cover p/s u/g n ok
ELE20-02757 Electrical Rough-In8/11/20208/12/20208/12/2020 9:45:13 AMACANC
Please call Chris for R/I of west stairwell conduit and boxes. Thanks!!!! Phone #: ###-#### Inspection requested via web by Rafael Castillo Dupicate request.
ELE20-02757 Electrical Rough-In8/11/20208/12/20208/12/2020 9:44:40 AMAPASS
Please call Chris for R/I of west stairwell conduit and boxes. Thanks!!!! Phone #: ###-#### Inspection requested via web by Rafael Castillo Level 1 west stair pour rough in ok cover.
ELE19-02700 Electrical Rough-In8/11/20208/12/20208/12/2020 9:27:36 AMAPASS
Switchgear inspection to energize.
Contact Brandon Robinson
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek OK to energize switch gear 2NHASWD.
ELE19-03829 Electrical Rough-In8/11/20208/12/20208/12/2020 9:05:33 AMAPASS
5th Floor bathrooms hard lids and 9th Floor walls.
Contact Shawn Evins.
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Level 1 west entries interior and exterior, Level 5 bathroom hard lids, Level 10 core walls as noted on contractor print rough in ok cover.
ELE19-03624 Electrical Rough-In8/10/20208/12/20208/11/2020 2:04:29 PMPCANC
Rough in for cover of hood vent in kitchen
Contact Alex Ybarra
Thank you, Phone #: ###-#### >> Inspection requested via web by Cathy Duchek Inspection cancelled from web by: Cathy Duchek
ELE19-03624 Electrical Rough-In8/10/20208/12/20208/10/2020 12:48:24 PMACANC
Rough in for cover of hood vent in kitchen.
Contact Alex Ybarra
Thank you, Phone #: ###-#### >> Inspection requested via web by Cathy Duchek Inspection cancelled from web by: Cathy Duchek