Inspections for the day of: Wednesday, August 12, 2020.
Number of inspections: 19
Percentage of inspections complete: 47 %
Percentage of inspections not complete: 53 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00865 FIR-Aging Inspection8/6/20208/6/2020   
FIR14-00895 FIR-Aging Inspection8/6/20208/6/2020   
FIR15-00132 FIR-Aging Inspection8/6/20208/6/2020   
FIR13-00218 FIR-Aging Inspection8/7/20208/7/2020   
FIR14-00238 FIR-Aging Inspection8/7/20208/7/2020   
FIR14-00684 FIR-Aging Inspection8/10/20208/10/2020   
FIR14-00827 FIR-Aging Inspection8/11/20208/11/2020   
FIR15-00163 FIR-Aging Inspection8/11/20208/11/2020   
FIR15-00155 FIR-Aging Inspection8/11/20208/11/2020   
FIR13-00629 FIR-Aging Inspection8/12/20208/12/20208/12/2020 7:56:51 PM CANC
FIR20-00195 INSP-Final Inspection8/11/20208/12/20208/12/2020 3:10:26 PMPFAIL
Not ready for a final yet. Inspection turned into a conference to address several areas that will need the notification adjusted and/or added due to partial height walls with curtains and chalk boards. Provide verification that all current draw for existing devices has been included in calcs.

Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
BLD19-00534 FIRE-Final Inspection8/11/20208/12/20208/12/2020 3:08:07 PMPFAIL
Life safety will be ok for a temp when the additional pavement has been layed as agreed. For a final the permanant address and heaters will need to be provided and veriifed.

Lee *screened Phone #: ###-####
FIR20-00046 INSP-Sprinkler Rough-in8/12/20208/12/20208/12/2020 12:12:33 PMPFAIL
Installation does not match plans, pendants have been added in areas and deleted in others. Missing one hanger.

Richard Clark is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
BLD20-01087 FIRE-Final Inspection8/12/20208/12/20208/12/2020 11:02:22 AMPPASS
Life safety passed.

Please call Jared ###-#### 15 minutes prior to inspection. Phone #: ###-#### Inspection requested via web by Jared Waggoner
BLD20-01088 FIRE-Final Inspection8/12/20208/12/20208/12/2020 11:01:57 AMPPASS
Life safety passed.

Please call Jared ###-#### 15 minutes prior to inspection. Phone #: ###-#### Inspection requested via web by Jared Waggoner
FIR20-00333 INSP-Final Inspection8/12/20208/12/20208/12/2020 11:01:36 AMPPASS
Permit finaled.

JARED FROM RUSSELL CORP. Phone #: ###-#### Inspection requested via web by Matthew Lewis
FIR20-00332 INSP-Final Inspection8/12/20208/12/20208/12/2020 11:01:13 AMPPASS
Permit finaled

JARED FROM RUSSELL CORP Phone #: ###-#### Inspection requested via web by Matthew Lewis
FIR19-00792 INSP-Sprinkler Rough-in/Hydro8/12/20208/12/20208/12/2020 10:41:34 AMPPASS
Overhead hydro of the 3rd and 4th floors witnessed with no pressure loss.

Screened- Tanner Phone #: ###-####
FIR11-00296 FIR-Aging Inspection8/12/20208/12/2020