Inspections for the day of: Monday, August 13, 2007.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-00352 FIRE-Final Inspection8/13/20078/13/20078/14/2007 11:44:43 AMPPART
Final pending project related fire sprinkler permit calc. verifications.
FIR07-00134 FIR-Aging Inspection8/13/20078/13/20078/14/2007 11:39:43 AM PART
Work in progress.
MIS07-00127 FIR-Final8/13/20078/13/20078/14/2007 11:38:10 AMPPASS
Fire life safety inspection completed satisfactory.
FIR07-00446 INSP-Sprinkler Rough-in8/10/20078/13/20078/13/2007 3:59:41 PMPPART
OH install is approved except as highlighted on approved plans for areas not completed including two stairways and the antifreeze loop, also noted one missing hanger on the 2nd floor, discussed WPI and FDC locations as well.
FIR07-00474 INSP-Final Inspection8/10/20078/13/20078/13/2007 3:56:05 PMPPART
Begin air test at 3:30@ 49psig.
FIR07-00485 INSP-Final Inspection8/13/20078/13/20078/13/2007 1:49:05 PMPPASS
Fire sprinkler final inspection passed, permit finaled.
BLD06-00908 FIRE-Final Inspection8/10/20078/13/20078/13/2007 12:53:52 PMAPASS
Noted items corrected, fire life safety inspection passed
FIR07-00316 INSP-Sprinkler Rough-in/Hydro8/10/20078/13/20078/13/2007 12:49:15 PMAFAIL
UG hydrostatic test failed due to pressure drop below 200 psi, guage appears damaged and may need to be replaced for accurate readings.
BLD07-01441 FIRE-Final Inspection8/10/20078/13/20078/13/2007 11:50:12 AMANR
Missing address numbers, door hardware, see fire code review notes for general requirements.
BLD07-01067 FIRE-Final Inspection8/10/20078/13/20078/13/2007 11:48:15 AMAFAIL
Need to post building address numbers, provide one additional PFE for the mezzanine office area, door hardware is not yet installed at several locations for verification of code compliance, post signage above the main entry/exit door and provide visual indicator, need to test EM lighting and exit signs at next visit.
BLD07-01120 FIRE-Final Inspection8/10/20078/13/20078/13/2007 11:19:07 AMACANC
curt Phone #: ###-#### Wrong permit number called per conversation with contractor.
BLD07-00352 FIRE-Final Inspection8/10/20078/13/20078/13/2007 11:12:38 AMANR
Inspection cancelled per phone call from contractor, pending related project permits.
FIR07-00462 INSP-Final Inspection8/13/20078/13/20078/13/2007 10:49:36 AMPCANC
rick - please call 1/2 hr prior to inspection Phone #: ###-#### Inspection cancelled from web by: Cathy Chiles
BLD07-01266 FIRE-Final Inspection8/10/20078/13/20078/13/2007 10:46:57 AMAPASS
Fire life safety inspection completed satisfactory.
FIR07-00498 INSP-Final Inspection8/13/20078/13/20078/13/2007 10:42:39 AMPPASS
As-builts provided, fire alarm permit finaled.
FIR07-00512 INSP-Final Inspection8/10/20078/13/20078/13/2007 10:41:03 AMAPASS
Final fire sprinkler inspection passed, permit finaled.
BLD07-02018 FIRE-Final Inspection8/10/20078/13/20078/13/2007 10:20:19 AMAFAIL
Provide approved hardware at the restroom and back exit doors as per approved plans and on site discussion.
FIR07-00593 INSP-Sprinkler Rough-in/Hydro8/11/20078/13/20078/13/2007 12:00:00 AMPCANC
Scheduled by a contractor via Hello! on 8/11/2007 at 11:52:57 AM. Contact: ###-####.