ELE08-01258
| ELE-Aging Inspection | 8/13/2008 | 8/13/2008 | 8/14/2008 12:07:30 PM | | PART |
|
|
wsuc
|
ESC08-00075
| General Inspection | 8/13/2008 | 8/13/2008 | 8/13/2008 4:27:41 PM | P | PART |
|
|
ok
|
ELE08-00657
| Final | 8/13/2008 | 8/13/2008 | 8/13/2008 4:25:22 PM | P | FAIL |
|
|
Pool room should be unlocked. Phone #: ###-#### Internet Inspection Request from: Lynn Cable corr called pool equip. panelboard/control cabinet has ETL sticker but does not state what it is just states conforms to UL and CSA
|
ESC07-01125
| General Inspection | 8/13/2008 | 8/13/2008 | 8/13/2008 3:25:24 PM | P | PART |
|
|
ok
|
ELE08-02276
| Temporary Service | 8/13/2008 | 8/13/2008 | 8/13/2008 3:24:39 PM | P | PASS |
|
|
Kevin ###-#### t/s u/g new ok
|
ELE08-01459
| Final | 8/13/2008 | 8/13/2008 | 8/13/2008 3:22:57 PM | P | PASS |
|
|
Call for access Phone #: ###-#### ok no card posted
|
ELE08-02099
| Electrical Rough-In | 8/13/2008 | 8/13/2008 | 8/13/2008 2:33:06 PM | P | NH |
|
|
Phone #: ###-#### Internet Inspection Request from: Lee Braithwait called left message posted notice
|
ESC07-01254
| General Inspection | 8/13/2008 | 8/13/2008 | 8/13/2008 1:58:23 PM | P | PART |
|
|
site ok
|
ELE08-02184
| Final | 8/13/2008 | 8/13/2008 | 8/13/2008 1:57:27 PM | P | FAIL |
|
|
Please call John to set up time for inspection. Phone #: ###-#### Internet Inspection Request from: John Campbell corr called 600.4 & 110.2 shall provide all manufacture"s marks and ratings, also listing and label, 600.5(C)(3) &410.30(B) grd pole at handhole remove or support box
|
ELE08-02103
| Electrical Rough-In | 8/13/2008 | 8/13/2008 | 8/13/2008 1:25:54 PM | P | PASS |
|
|
Randy is the contact, his cell # is ###-####. Thank you. Phone #: ###-#### Internet Inspection Request from: Shawna Gates no esc r/i ok
|
ELE08-02103
| Final | 8/13/2008 | 8/13/2008 | 8/13/2008 1:25:30 PM | P | PASS |
|
|
Randy is the contact, his cell # is ###-####. Thank you. Phone #: ###-#### Internet Inspection Request from: Shawna Gates final ok contr will supply 3 pole breaker od handle tie for 3 1pole breakers to meet 210.4, (B)
|
ESC08-00215
| General Inspection | 8/13/2008 | 8/13/2008 | 8/13/2008 12:30:00 PM | P | PART |
|
|
site ok
|
ELE08-02268
| Electrical Rough-In | 8/12/2008 | 8/13/2008 | 8/13/2008 12:29:11 PM | A | FAIL |
|
|
Tenant improvement (south side suite) for cover. Reception area and break room to be drop accoustical tile ceilings. Exam room to be sheetrock ceiling. Phone #: ###-#### Internet Inspection Request from: Joe Thomas need approved plans at site for tennat space called
|
ELE08-02267
| Rough-In Permanent Service | 8/12/2008 | 8/13/2008 | 8/13/2008 12:28:21 PM | A | FAIL |
|
|
Core and shell for cover and perm. service. Core and shell covers 400 Amp serv., 2 200 amp panels, bathrooms, mechanical room, foyer, and exterior lighting. HVAC: 1 outdoor unit on rooftop SE corner. 1 indoor unit in hallway. Foyer to be sheetrock ceiling. Hall, baths, and mech. room to be drop accoustical tile. Phone #: ###-#### Internet Inspection Request from: Joe Thomas corr called need approved set of plans at site, 210.25(B) all common area circuits shall be on house panel only and shall feed only common area circuits
|
ESC08-00193
| General Inspection | 8/13/2008 | 8/13/2008 | 8/13/2008 10:54:14 AM | A | PART |
|
|
ok contr has water truck coming today for dust
|
ELE08-01805
| Electrical Rough-In | 8/12/2008 | 8/13/2008 | 8/13/2008 10:53:18 AM | A | PART |
|
|
Inspection for cover on the walls Phone #: ###-#### Internet Inspection Request from: Spencer Mclean walls hard ceilings ok corr 210.62 needs to address show window recepts entry area and 3 N facing windows
|
ELE08-02258
| Electrical Rough-In | 8/12/2008 | 8/13/2008 | 8/13/2008 10:01:37 AM | A | FAIL |
|
|
Electrical ready for the cover inspection Phone #: ###-#### Internet Inspection Request from: Spencer Mclean job on hold till owner get permits and approved plans, note owner told me basement apartment is for his mother org. bld does not allow work in basement called
|
ESC08-00361
| General Inspection | 8/13/2008 | 8/13/2008 | 8/13/2008 8:53:16 AM | A | PART |
|
|
ok
|
ELE08-02243
| Electrical Rough-In | 8/12/2008 | 8/13/2008 | 8/13/2008 8:52:34 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 8/12/2008 at 9:45:14 PM. Contact: ###-####. garage ok, new addition walls ceilings ok
|
ELE08-02103
| Final | 8/12/2008 | 8/13/2008 | 8/13/2008 7:48:31 AM | P | CANC |
|
|
RANDY IS THE ONSITE CONTACT, HIS CELL # IS
###-####. THANK YOU. Phone #: ###-#### Internet Inspection Request from: Shawna Gates Inspection cancelled from web by: Shawna Gates
|