Inspections for the day of: Wednesday, August 13, 2008.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00496 INSP-Final Inspection8/13/20088/13/20088/14/2008 10:32:22 AMPPASS
Noted corrections verified for completion, after hours fire alarm testing passed, permit finaled.
BLD08-01271 FIRE-Final Inspection8/12/20088/13/20088/14/2008 10:10:29 AMPFAIL
Install missing ceiling tile at sprinkler head in a storage closet on the north side, provide one additional exit sign as discussed, clear trouble at the FACP due to missing smoke heads, blank hardware at one door no longer in use.
FIR08-00462 INSP-Final Inspection8/13/20088/13/20088/13/2008 5:22:23 PMPPASS
Fire sprinkler permit finaled.
BLD07-02566 FIRE-Final Inspection8/13/20088/13/20088/13/2008 4:42:06 PMPPASS
Life safety finaled.
BLD08-00151 FIRE-Final Inspection8/12/20088/13/20088/13/2008 4:41:34 PMAPASS
Fire life safety passed.
BLD08-01549 FIRE-Final Inspection8/12/20088/13/20088/13/2008 12:57:04 PMAPASS
Fire life safety inspection passed.
BLD08-01363 FIRE-Conference8/12/20088/13/20088/13/2008 12:36:21 PMADONE
On site conference regarding fire code review notes, egress lighting, exit discharge, and HVAC system duct detectors.
FIR08-00463 INSP-Sprinkler Rough-in/Hydro8/12/20088/13/20088/13/2008 12:29:12 PMAPART
See red-lined locations on plans for areas okayed for ceiling cover, also noted two rooms and the reception area not yet complete.
BLD08-00177 FIRE-Final Inspection8/12/20088/13/20088/13/2008 12:25:42 PMAFAIL
Repair exit signs and emergency lighting at four locations, remainder of life safety items acceptable.
BLD08-00753 FIRE-Final Inspection8/12/20088/13/20088/13/2008 12:23:10 PMAFAIL
Need to repair one exit sign at the south side, provide EM lights for the path of egress, fire alarm okayed.