FIR08-00532
| INSP-Final Inspection | 8/13/2008 | 8/13/2008 | 8/13/2008 4:23:49 PM | P | FAIL |
|
|
This project is not ready for a final inspection but was ready for a rough-in inspection. The sprinkler piping is ok to cover.
|
FIR06-00871
| INSP-Conference | 8/13/2008 | 8/13/2008 | 8/13/2008 4:22:42 PM | P | DONE |
|
|
I spoke to MIke with Peak Alarm about getting this permit finaled. He stated that he would make sure to get it scheduled if it had not been already signed off when the HeadMasters School opened.
|
BLD08-01616
| FIRE-Final Inspection | 8/13/2008 | 8/13/2008 | 8/13/2008 3:15:54 PM | P | PASS |
|
|
Life safety passed
|
BLD08-00984
| FIRE-Final Inspection | 8/12/2008 | 8/13/2008 | 8/13/2008 1:57:13 PM | A | FAIL |
|
|
The project related fire alarm permit needs to be finaled. Also the very west most second floor corridor exit sign needs repaired and another needs to be added at the second floor elevator corridor/main corridor junction as shown on the city approved drawings. All other items are ok.
|
FIR08-00397
| INSP-Final Inspection | 8/12/2008 | 8/13/2008 | 8/13/2008 1:55:37 PM | A | FAIL |
|
|
All of the previous deficiencies have been corrected. Once we were able to test the audio/visual devices we found that the second floor horns are not syncronized as required per NFPA 72 - 6.8.6.5.3. The duct smoke detectors tested ok.
|
BLD08-01431
| FIRE-Final Inspection | 8/12/2008 | 8/13/2008 | 8/13/2008 9:40:48 AM | A | PASS |
|
|
life safety passed
|