FIR09-00290
| INSP-Final Inspection | 8/13/2009 | 8/13/2009 | 8/13/2009 6:03:46 PM | P | FAIL |
|
|
Two notification appliances at the perishables office are non-functional (one repaired while on site) billing office a/v needs retested, NAC 10 circut 1 horns are not working, NAC 10 circut 3 horns at the dry produce section are not functional-also missing horn appliance at the EOL this circut. Retest for moved MP at the SE dock and added a/v in the breakroom tested okay, horns and MP's as marked on plan set sheets F-3,F-4 and F-5 also okayed including dock area and dairy, grocery, meat and deli coolers. Dry and wet produce coolers need notification retest.
|
FIR09-00292
| FIR-Aging Inspection | 8/13/2009 | 8/13/2009 | 8/13/2009 5:52:16 PM | | DONE |
|
|
Pending site inspection request when work is finished.
|
BLD07-01910
| FIRE-Final Inspection | 8/13/2009 | 8/13/2009 | 8/13/2009 5:51:17 PM | P | NR |
|
|
Notified contractor that project related FIR permit for hood suppression must first be finaled prior to fire life safety.
|
FIR09-00442
| INSP-Final Inspection | 8/12/2009 | 8/13/2009 | 8/13/2009 5:50:06 PM | P | NR |
|
|
Project is not ready for final, walls to separate sprinklered and non-sprinklered areas are not built, the new storage room as shown on building plans is not drawn on sprinkler plans-coverage to be verified when room is constructed, new mechanical room per the scope of building permit work is not properly protected, noted main and branchline pipe sizes have been changed per red-lines.
|
FIR09-00461
| INSP-Final Inspection | 8/12/2009 | 8/13/2009 | 8/13/2009 5:22:11 PM | A | PASS |
|
|
Hood suppression system functioned properly under test conditions, permit finaled.
|