Inspections for the day of: Thursday, August 13, 2009.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00290 INSP-Final Inspection8/13/20098/13/20098/13/2009 6:03:46 PMPFAIL
Two notification appliances at the perishables office are non-functional (one repaired while on site) billing office a/v needs retested, NAC 10 circut 1 horns are not working, NAC 10 circut 3 horns at the dry produce section are not functional-also missing horn appliance at the EOL this circut. Retest for moved MP at the SE dock and added a/v in the breakroom tested okay, horns and MP's as marked on plan set sheets F-3,F-4 and F-5 also okayed including dock area and dairy, grocery, meat and deli coolers. Dry and wet produce coolers need notification retest.
FIR09-00292 FIR-Aging Inspection8/13/20098/13/20098/13/2009 5:52:16 PM DONE
Pending site inspection request when work is finished.
BLD07-01910 FIRE-Final Inspection8/13/20098/13/20098/13/2009 5:51:17 PMPNR
Notified contractor that project related FIR permit for hood suppression must first be finaled prior to fire life safety.
FIR09-00442 INSP-Final Inspection8/12/20098/13/20098/13/2009 5:50:06 PMPNR
Project is not ready for final, walls to separate sprinklered and non-sprinklered areas are not built, the new storage room as shown on building plans is not drawn on sprinkler plans-coverage to be verified when room is constructed, new mechanical room per the scope of building permit work is not properly protected, noted main and branchline pipe sizes have been changed per red-lines.
FIR09-00461 INSP-Final Inspection8/12/20098/13/20098/13/2009 5:22:11 PMAPASS
Hood suppression system functioned properly under test conditions, permit finaled.