Inspections for the day of: Thursday, August 13, 2009.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00408 INSP-Supply line flush8/13/20098/13/20098/14/2009 11:31:46 AMPPART
The underground supply piping is ok to cover except where the thrust blocks are needed.
FIR08-00720 INSP-Final Inspection8/12/20098/13/20098/13/2009 3:42:10 PMPPASS
Permit finaled.
FIR09-00455 INSP-Final Inspection8/12/20098/13/20098/13/2009 3:41:37 PMAFAIL
All items have been corrected except now the exhaust fan is shutting down during activation of the suppression system which it can not do.
FIR09-00454 INSP-Sprinkler Rough-in/Hydro8/12/20098/13/20098/13/2009 3:40:24 PMAFAIL
Too many heads have been supplied from a single 1" outlet without verification of meeting all requirements of the use of Room Design method. Don and I discussed this topic extensively and he is going to follow up on wall ratings or provide separate supplies. Also insulation in hanging down from the deck blocking sprinkler coverage.
FIR09-00456 INSP-Sprinkler Rough-in/Hydro8/12/20098/13/20098/13/2009 12:03:22 PMAPART
See the city approved plans for locations where piping is approved
FIR09-00424 INSP-Sprinkler Rough-in/Hydro8/12/20098/13/20098/13/2009 10:57:54 AMAPASS
The 24 air test passed.