BLD12-00636
| FIRE-Final Inspection | 8/13/2012 | 8/13/2012 | 8/13/2012 3:51:08 PM | P | FAIL |
|
|
Provide a fire extinguisher as discussed.
|
FIR12-00266
| INSP-Sprinkler Rough-in | 8/13/2012 | 8/13/2012 | 8/13/2012 3:37:18 PM | P | PASS |
|
|
Overhead/hydrostatic test for both wet and dry systems passed.
|
FIR12-00109
| INSP-Supply line flush | 8/13/2012 | 8/13/2012 | 8/13/2012 3:32:32 PM | P | PASS |
|
|
Underground flush passed
|
FIR11-00543
| INSP-Sprinkler Rough-in/Hydro | 8/13/2012 | 8/13/2012 | 8/13/2012 3:31:10 PM | P | FAIL |
|
|
Hydro inspection for the overhead system failed due to visable pressure loss at all three guages.
|
BLD12-01188
| FIRE-Final Inspection | 8/10/2012 | 8/13/2012 | 8/13/2012 1:38:03 PM | A | CANC |
|
|
rescheduled for tomorrow per contractor.
|
BLD12-02057
| FIRE-Final Inspection | 8/13/2012 | 8/13/2012 | 8/13/2012 12:59:12 PM | P | PASS |
|
|
life safety passed
|
FIR12-00330
| INSP-Sprinkler Rough-in/Hydro | 8/13/2012 | 8/13/2012 | 8/13/2012 10:12:18 AM | P | CANC |
|
|
To be resceduled for tomorrow per Dale Phone #: ###-####
|
FIR12-00376
| INSP-Final Inspection | 8/10/2012 | 8/13/2012 | 8/13/2012 10:01:42 AM | A | FAIL |
|
|
The underground water supply has been turned off so no testing can be completed.
|
FIR12-00347
| INSP-Final Inspection | 8/10/2012 | 8/13/2012 | 8/13/2012 9:15:50 AM | A | FAIL |
|
|
The underground water supply has been turned off so no testing can be completed.
|
BLD12-02057
| FIRE-Final Inspection | 8/10/2012 | 8/13/2012 | 8/13/2012 8:27:38 AM | A | FAIL |
|
|
Remove the thumbturn lock from the rear exit door.
|