Inspections for the day of: Monday, August 13, 2012.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD12-00636 FIRE-Final Inspection8/13/20128/13/20128/13/2012 3:51:08 PMPFAIL
Provide a fire extinguisher as discussed.
FIR12-00266 INSP-Sprinkler Rough-in8/13/20128/13/20128/13/2012 3:37:18 PMPPASS
Overhead/hydrostatic test for both wet and dry systems passed.
FIR12-00109 INSP-Supply line flush8/13/20128/13/20128/13/2012 3:32:32 PMPPASS
Underground flush passed
FIR11-00543 INSP-Sprinkler Rough-in/Hydro8/13/20128/13/20128/13/2012 3:31:10 PMPFAIL
Hydro inspection for the overhead system failed due to visable pressure loss at all three guages.
BLD12-01188 FIRE-Final Inspection8/10/20128/13/20128/13/2012 1:38:03 PMACANC
rescheduled for tomorrow per contractor.
BLD12-02057 FIRE-Final Inspection8/13/20128/13/20128/13/2012 12:59:12 PMPPASS
life safety passed
FIR12-00330 INSP-Sprinkler Rough-in/Hydro8/13/20128/13/20128/13/2012 10:12:18 AMPCANC
To be resceduled for tomorrow per Dale Phone #: ###-####
FIR12-00376 INSP-Final Inspection8/10/20128/13/20128/13/2012 10:01:42 AMAFAIL
The underground water supply has been turned off so no testing can be completed.
FIR12-00347 INSP-Final Inspection8/10/20128/13/20128/13/2012 9:15:50 AMAFAIL
The underground water supply has been turned off so no testing can be completed.
BLD12-02057 FIRE-Final Inspection8/10/20128/13/20128/13/2012 8:27:38 AMAFAIL
Remove the thumbturn lock from the rear exit door.