Inspections for the day of: Tuesday, August 13, 2013.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD13-01714 FIRE-Sprinkler Rough-in8/13/20138/13/20138/13/2013 5:16:29 PMPPART
Overhead fire sprinkler work approved for cover.
FIR13-00300 INSP-Final Inspection8/13/20138/13/20138/13/2013 5:15:18 PMAPASS
Fire sprinkler permit approved for final.
FIR13-00264 INSP-Sprinkler Rough-in8/12/20138/13/20138/13/2013 5:11:51 PMAPART
Completed overhead rough-in of the new wet and dry systems. Noted one missing EQ brace at the lower level 4" main, provide seismic clearance at the main through masonry wall west end. Additional uprights and branchline to be shown on record drawings. Non-sprinklered combustible concealed pockets to be filled with insulation as discussed with contractor to meet the allowable exceptions per NFPA. Discussed hydro and air testing, riser room yet to be built, FDC location, etc.