FIR15-00517
| INSP-Sprinkler Rough-in | 8/13/2015 | 8/13/2015 | 8/13/2015 3:36:55 PM | P | PART |
|
|
Inspection was a cover for the underground supply. Not all of the underground was installled so see the city approved plans for exact location where piping is ok to cover.
|
FIR15-00522
| INSP-Final Inspection | 8/11/2015 | 8/13/2015 | 8/13/2015 3:27:48 PM | P | FAIL |
|
|
Alarm; John
No contact phone number was given, I went to the job site and no one was there. No one in the U Haul office knew anything. Permit is for underground sprinkler. No inspection performed.
|
BLD15-02652
| FIRE-Final Inspection | 8/13/2015 | 8/13/2015 | 8/13/2015 2:02:16 PM | P | PASS |
|
|
life safety passed
|
FIR15-00143
| INSP-Sprinkler Rough-in/Hydro | 8/13/2015 | 8/13/2015 | 8/13/2015 1:57:14 PM | P | PASS |
|
|
Overhead hydro test passed
|
FIR15-00222
| INSP-Sprinkler Rough-in/Hydro | 8/13/2015 | 8/13/2015 | 8/13/2015 1:23:54 PM | P | FAIL |
|
|
Overhead hydro test failed due to visible loss at guage.
|
FIR15-00223
| INSP-Sprinkler Rough-in/Hydro | 8/13/2015 | 8/13/2015 | 8/13/2015 1:22:59 PM | P | FAIL |
|
|
Above ground hydro test failed due to visible loss at guage
|
FIR15-00031
| INSP-Final Inspection | 8/12/2015 | 8/13/2015 | 8/13/2015 12:29:36 PM | A | FAIL |
|
|
We tested the elevator and it did recall the elevator but did not set off the new notification circuits. Tested some of the hvac units but could not get all of them to turn on. When notification circuits were activated there is sync issue. Testing stopped.
|
BLD14-02241
| FIRE-Final Inspection | 8/12/2015 | 8/13/2015 | 8/13/2015 11:28:36 AM | A | FAIL |
|
|
Only tested the exit signs and emergency lights will finish inspection when the project related fire alarm permit/corrections have been made.
|
FIR15-00217
| INSP-Sprinkler Rough-in | 8/12/2015 | 8/13/2015 | 8/13/2015 11:17:22 AM | A | PASS |
|
|
Tenting and rough-in passed. Piping can be covered.
|
BLD15-02577
| FIRE-Final Inspection | 8/11/2015 | 8/13/2015 | 8/13/2015 9:13:06 AM | A | FAIL |
|
|
I left message on contacts phone that I was on the way. Arrived at job site and front door was locked and contact not there. I went around back and found warehouse open. Per review comments there is to be no storage over 12'. Storage is over 12'. Chris Phone #: ###-####
|