Inspections for the day of: Thursday, August 13, 2015.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00517 INSP-Sprinkler Rough-in8/13/20158/13/20158/13/2015 3:36:55 PMPPART
Inspection was a cover for the underground supply. Not all of the underground was installled so see the city approved plans for exact location where piping is ok to cover.
FIR15-00522 INSP-Final Inspection8/11/20158/13/20158/13/2015 3:27:48 PMPFAIL
Alarm; John

No contact phone number was given, I went to the job site and no one was there. No one in the U Haul office knew anything. Permit is for underground sprinkler. No inspection performed.
BLD15-02652 FIRE-Final Inspection8/13/20158/13/20158/13/2015 2:02:16 PMPPASS
life safety passed
FIR15-00143 INSP-Sprinkler Rough-in/Hydro8/13/20158/13/20158/13/2015 1:57:14 PMPPASS
Overhead hydro test passed
FIR15-00222 INSP-Sprinkler Rough-in/Hydro8/13/20158/13/20158/13/2015 1:23:54 PMPFAIL
Overhead hydro test failed due to visible loss at guage.
FIR15-00223 INSP-Sprinkler Rough-in/Hydro8/13/20158/13/20158/13/2015 1:22:59 PMPFAIL
Above ground hydro test failed due to visible loss at guage
FIR15-00031 INSP-Final Inspection8/12/20158/13/20158/13/2015 12:29:36 PMAFAIL
We tested the elevator and it did recall the elevator but did not set off the new notification circuits. Tested some of the hvac units but could not get all of them to turn on. When notification circuits were activated there is sync issue. Testing stopped.
BLD14-02241 FIRE-Final Inspection8/12/20158/13/20158/13/2015 11:28:36 AMAFAIL
Only tested the exit signs and emergency lights will finish inspection when the project related fire alarm permit/corrections have been made.
FIR15-00217 INSP-Sprinkler Rough-in8/12/20158/13/20158/13/2015 11:17:22 AMAPASS
Tenting and rough-in passed. Piping can be covered.
BLD15-02577 FIRE-Final Inspection8/11/20158/13/20158/13/2015 9:13:06 AMAFAIL
I left message on contacts phone that I was on the way. Arrived at job site and front door was locked and contact not there. I went around back and found warehouse open. Per review comments there is to be no storage over 12'. Storage is over 12'. Chris Phone #: ###-####