ELE19-03624
| Electrical Rough-In | 8/11/2020 | 8/13/2020 | 8/13/2020 2:36:33 PM | P | PASS |
|
|
Rough in for cover of hood vent in kitchen Contact Alex Ybarra Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Hood hard wired, rough in ok cover
|
ELE20-00988
| Electrical Rough-In | 8/13/2020 | 8/13/2020 | 8/13/2020 2:05:12 PM | P | PASS |
|
|
Contact: Jeremy Thornock, underground inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden Service entrance conduits rough in ok cover.
|
ELE20-02300
| Conference | 8/13/2020 | 8/13/2020 | 8/13/2020 1:25:04 PM | P | PASS |
|
|
Discuss grounding and bonding Phone #: ###-#### Inspection requested via web by Jason Parke Discussed the installation of a common grounding electrode conductor from level 1 service location to the other service locations and tapping off to provide a grounding electrode conductor to each service. As long as connection comply with 250.64 and are listed for grounding and bonding... plan looks good. Thanks.
|
ELE20-02569
| Final | 8/13/2020 | 8/13/2020 | 8/13/2020 12:31:00 PM | P | PASS |
|
|
Our permit is for conduit work from disconnect up light pole. Pole located on S.W. Corner of Parkcenter and River Run Dr. Phone #: ###-#### Inspection requested via web by Troy Hughes Final ok
|
ELE20-02864
| Electrical Rough-In | 8/12/2020 | 8/13/2020 | 8/13/2020 11:49:33 AM | A | PASS |
|
|
Please call Matthew Jones prior to arriving on site. Thanks. Phone #: ###-#### Inspection requested via web by Nicholas Buck Line side tap due to hard to find breakers. Listings confirmed. Rough in ok cover
|
ELE19-03064
| Electrical Rough-In | 8/12/2020 | 8/13/2020 | 8/13/2020 11:32:37 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Garrett Collins Rough in ok cover
|
ELE19-03064
| Permanent Service | 8/12/2020 | 8/13/2020 | 8/13/2020 11:32:02 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Garrett Collins Grounding electrode located in storage under stairs. p/s u/g n ok
|
ELE20-01695
| Electrical Rough-In | 8/12/2020 | 8/13/2020 | 8/13/2020 10:07:48 AM | A | PASS |
|
|
1st and 2nd floor common areas for cover Phone #: ###-#### Inspection requested via web by kendall bender City approved set of prints on site confirmed. Level 1 and 2 common areas floors, walls, ceilings rough in ok cover
|
ELE19-03829
| Electrical Rough-In | 8/12/2020 | 8/13/2020 | 8/13/2020 9:24:52 AM | A | PASS |
|
|
6th floor restroom ceilings. Contact Shawn Evins. Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Areas noted as noted on contractor print rough in ok cover.
|
ELE20-02769
| Final | 8/13/2020 | 8/13/2020 | 8/13/2020 8:59:34 AM | P | PASS |
|
|
Our permit is for conduits from disconnect up light pole. Pole located on S.W. corner of Emerald St. and N. Roosevelt St. Phone #: ###-#### Inspection requested via web by Troy Hughes Final ok
|
ELE20-02352
| Final | 8/12/2020 | 8/13/2020 | 8/13/2020 8:59:07 AM | A | PASS |
|
|
The disconnect is ready for final inspection. Ohm report has been sent to inspector. Please call Joe with questions. ###-#### Phone #: ###-#### Inspection requested via web by Joe McLean Final ok
|