FIR15-00002
| FIR-Aging Inspection | 8/6/2020 | 8/6/2020 | | | |
|
|
|
FIR15-00156
| FIR-Aging Inspection | 8/6/2020 | 8/6/2020 | | | |
|
|
|
FIR13-00368
| FIR-Aging Inspection | 8/7/2020 | 8/7/2020 | | | |
|
|
|
FIR14-00194
| FIR-Aging Inspection | 8/7/2020 | 8/7/2020 | | | |
|
|
|
FIR14-00774
| FIR-Aging Inspection | 8/7/2020 | 8/7/2020 | | | |
|
|
|
FIR08-00387
| FIR-Aging Inspection | 8/10/2020 | 8/10/2020 | | | |
|
|
|
FIR13-00607
| FIR-Aging Inspection | 8/10/2020 | 8/10/2020 | | | |
|
|
|
FIR14-00195
| FIR-Aging Inspection | 8/10/2020 | 8/10/2020 | | | |
|
|
|
FIR14-00490
| FIR-Aging Inspection | 8/10/2020 | 8/10/2020 | | | |
|
|
|
FIR15-00023
| FIR-Aging Inspection | 8/11/2020 | 8/11/2020 | | | |
|
|
|
FIR15-00119
| FIR-Aging Inspection | 8/11/2020 | 8/11/2020 | | | |
|
|
|
FIR11-00561
| FIR-Aging Inspection | 8/12/2020 | 8/12/2020 | | | |
|
|
|
FIR12-00309
| FIR-Aging Inspection | 8/12/2020 | 8/12/2020 | | | |
|
|
|
FIR14-00728
| FIR-Aging Inspection | 8/12/2020 | 8/12/2020 | | | |
|
|
|
BLD19-02564
| FIRE-Final Inspection | 8/13/2020 | 8/13/2020 | 8/13/2020 4:48:00 PM | P | PASS |
|
|
Door hardware complies with 2015 IFC section 1010.1.9.9 with push button and motion sensor accessories. Final life fire safety inspection for scope of work is complete.
screened - there have been school employees inside // Mike Phone #: ###-####
|
BLD19-04518
| FIRE-Final Inspection | 8/13/2020 | 8/13/2020 | 8/13/2020 4:33:17 PM | P | PART |
|
|
Life fire safety inspection for phase 3A complete.
Requesting a fire life inspection in Phase 3A. please give me a call 30 minutes in advice if possible to allow tie for my electrician to be onsite for assistance. Please contact Markus Schlegel if you have questions. Phone #: ###-#### Inspection requested via web by Markus Schlegel
|
BLD20-01775
| FIRE-Final Inspection | 8/13/2020 | 8/13/2020 | 8/13/2020 3:13:27 PM | P | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, locking hardware on sliding glass doors was rem oved during inspection. Final life fire inspection for scope of work is complete, signature card not available at time of inspection.
*screened* Zach Phone #: ###-####
|
FIR19-00839
| INSP-Sprinkler Rough-in | 8/13/2020 | 8/13/2020 | 8/13/2020 2:45:11 PM | P | PART |
|
|
Area marked with red ink on city approved drawings inspected, area marked is approved for cover.
Parcel in the open office area. Phone #: ###-#### Inspection requested via web by Brian Carlisle
|
BLD20-02428
| FIRE-Final Inspection | 8/13/2020 | 8/13/2020 | 8/13/2020 2:00:12 PM | P | PASS |
|
|
No fire sprinklers, no fire alarms, fire exitinguisher is placed with a current inspection tag. Final life fire safety inspection is complete, signature card not available at time of inspection.
Please call 30 mins ahead of time so I can meet you there. Phone #: ###-#### Inspection requested via web by Gerome Fries
|
BLD20-00796
| FIRE-Final Inspection | 8/6/2020 | 8/13/2020 | 8/13/2020 1:43:50 PM | A | PART |
|
|
Fire sprinkler inspection for TCO phase 1 complete, fire alarm for phase 1 TCO complete, fire extinguishers for TCO phase 1 area are placed with current inspection tags. Push button for access controlled doors to be raised between 40 to 48 inches as discussed. Three exit signs to be added and 2 too be relocated as discussed. Will verify noted items on final life fire safety phase 2 inspection. Life fire safety for TCO phase 1 is complete, signatures provided on permit sign off card for TCO phase 1.
Curt *screened* Phone #: ###-####
|
FIR20-00168
| INSP-Final Inspection | 8/12/2020 | 8/13/2020 | 8/13/2020 1:31:23 PM | A | PART |
|
|
Final fire sprinkler inspection for TCO phase 1 complete.
Richard Clark is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD20-00953
| FIRE-Final Inspection | 8/13/2020 | 8/13/2020 | 8/13/2020 11:07:48 AM | P | PASS |
|
|
Life fire safety inspection for racking complete.
Fred */Screened*/ Phone #: ###-####
|
FIR20-00521
| INSP-Final Inspection | 8/13/2020 | 8/13/2020 | 8/13/2020 11:07:23 AM | P | PASS |
|
|
Fire beel has been repaired, final fire sprinkler inspection is complete.
|
FIR20-00443
| INSP-Sprinkler Rough-in | 8/12/2020 | 8/13/2020 | 8/13/2020 11:05:47 AM | P | PASS |
|
|
Rough in inspection is complete, all tenting in place at time of inspection, cover is approved. Cover sticker has been placed.
tenting Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
FIR20-00436
| INSP-Sprinkler Rough-in | 8/12/2020 | 8/13/2020 | 8/13/2020 11:05:29 AM | P | PASS |
|
|
Rough in inspection is complete, all tenting in place at time of inspection, cover is approved. Cover sticker has been placed.
tenting Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
FIR20-00441
| INSP-Sprinkler Rough-in | 8/12/2020 | 8/13/2020 | 8/13/2020 11:05:10 AM | P | PASS |
|
|
Rough in inspection is complete, all tenting in place at time of inspection, cover is approved. Cover sticker has been placed.
tenting Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
FIR20-00447
| INSP-Sprinkler Rough-in | 8/12/2020 | 8/13/2020 | 8/13/2020 11:04:54 AM | P | PASS |
|
|
Rough in inspection is complete, all tenting in place at time of inspection, cover is approved. Cover sticker has been placed.
tenting Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
FIR20-00437
| INSP-Sprinkler Rough-in | 8/12/2020 | 8/13/2020 | 8/13/2020 11:04:05 AM | P | PASS |
|
|
All tenting in place at time of inspection, cover is approved, cover sticker has been placed.
tenting Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
FIR20-00390
| INSP-Sprinkler Rough-in | 8/12/2020 | 8/13/2020 | 8/13/2020 11:02:21 AM | A | PART |
|
|
Rough to cover inspection from between south connection too tank (Still about 10 feet of pipe left to install by tank) around too approxiamatly 5 sticks of pipe on north section complete (north piping runs west too east) complete, area inspected approved for cover.
Please call Clarence for the rough in on the underground. Phone #: ###-#### Inspection requested via web by Jessia McLain
|
BLD20-02420
| FIRE-Final Inspection | 8/12/2020 | 8/13/2020 | 8/13/2020 10:17:11 AM | A | PASS |
|
|
Furniture is placed as shown on city approved plans too get below square footage requirements for fire sprinklers as discussed with Joe Bruce, building is partially sprinklered. No fire sprinkler modifications, no fire alarms, system was installed when system size was not required to be monitored. Noted, any modifications too the fire sprinkler system will require fire sprinkler monitoring per IFC, fire extingiushers are placed with current inspection tags. Final life fire safety inspection is complete, signature provided on permit sign off card.
Ralph May, Call ###-####
|
FIR20-00104
| INSP-Sprinkler Rough-in | 8/13/2020 | 8/13/2020 | 8/13/2020 10:02:55 AM | P | CANC |
|
|
Contact Ken Orahood ###-#### 30 min prior to RTC Insp start please, this will be for the hard lids.
Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|
FIR20-00446
| INSP-Sprinkler Rough-in | 8/12/2020 | 8/13/2020 | 8/13/2020 9:02:12 AM | P | CANC |
|
|
Cancelled per conversation with point of contact, inspection will be rescheduled for a later date.
OH piping rough Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
FIR20-00440
| INSP-Sprinkler Rough-in | 8/12/2020 | 8/13/2020 | 8/13/2020 9:01:49 AM | P | CANC |
|
|
Cancelled per conversation with point if contact, inspection will be rescheduled for a later date.
OH piping rough Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
FIR20-00037
| INSP-Final Inspection | 8/11/2020 | 8/13/2020 | 8/13/2020 8:56:57 AM | A | CANC |
|
|
Cancelled per conversation with point of contact, inspection request will be rescheduled for a later date.
hey I hope you saw my notes on the other final elevator inspections Phone #: ###-#### Inspection requested via web by Trevor Reed
|
FIR19-00918
| INSP-Final Inspection | 8/11/2020 | 8/13/2020 | 8/13/2020 8:56:42 AM | A | CANC |
|
|
Cancelled per conversation with point of contact, inspection request will be rescheduled for a later date.
I will be calling in 4 of these final elevator inspections let me know if this is too much we will have the elevator company here to get us into the shaft and pit to test devices Phone #: ###-#### Inspection requested via web by Trevor Reed
|
FIR19-00496
| INSP-Final Inspection | 8/11/2020 | 8/13/2020 | 8/13/2020 8:56:26 AM | A | CANC |
|
|
Cancelled per conversation with point of contact, inspection request will be rescheduled for a later date.
this final inspection will be for a elevator and we will have 4 of these inspections to do on this day we will have the elevator company here to get us in the pit and top of the shaft to test devices. Jim let me know if this is too much to do on one day the elevator guys are not cheap to have out here. Phone #: ###-#### Inspection requested via web by Trevor Reed
|
FIR20-00302
| INSP-Final Inspection | 8/11/2020 | 8/13/2020 | 8/13/2020 8:55:21 AM | A | FAIL |
|
|
Smoke detecotr in front of elevator reported as a supervisory, needs to report as a general alram along with recall function.
I have called 4 of these final elevator inspections for Thursday AM let me know if you think this will be an issue. I will have the elevator guy here to get us into the shaft and pit Phone #: ###-#### Inspection requested via web by Trevor Reed
|
FIR20-00521
| INSP-Final Inspection | 8/12/2020 | 8/13/2020 | 8/13/2020 7:26:35 AM | A | FAIL |
|
|
Circuit breaker for bell is on, bell did not function on flow switch activation.
Colton Cox is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR20-00521
| INSP-Sprinkler Rough-in | 8/13/2020 | 8/13/2020 | 8/13/2020 7:25:57 AM | A | PASS |
|
|
All tenting in place at time of inspection. Rough in inspection is complete, cover has been approved.
|
FIR20-00159
| INSP-Supply line flush | 8/12/2020 | 8/13/2020 | 8/13/2020 6:17:01 AM | A | DONE |
|
|
Main underground supply flush witnessed.
*Screened* Underground Troy, requesting 6AM Phone #: ###-####
|
BLD20-00796
| FIRE-Alarm Testing | 8/12/2020 | 8/13/2020 | 8/12/2020 4:03:43 PM | A | CANC |
|
|
Fire alarm inspection has been requested under the fire alarm FIR permit, this request is cancelled.
Screened- Curtis Phone #: ###-####
|
FIR14-00868
| FIR-Aging Inspection | 8/13/2020 | 8/13/2020 | | | |
|
|
|
FIR15-00024
| FIR-Aging Inspection | 8/13/2020 | 8/13/2020 | | | |
|
|
|
FIR15-00041
| FIR-Aging Inspection | 8/13/2020 | 8/13/2020 | | | |
|
|
|
FIR15-00066
| FIR-Aging Inspection | 8/13/2020 | 8/13/2020 | | | |
|
|
|
MIS18-00382
| MIS-Aging Inspection | 8/13/2020 | 8/13/2020 | | | |
|
|
|