Inspections for the day of: Tuesday, August 14, 2001.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorAlan Hauser
TitleMEC-COM/RES INSPECTOR
Phone #794-9453
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD00-02862 BLD-Final8/13/20018/14/20018/14/2001 12:00:00 AMAFAIL
cover kraft paper on insulation in basement walls or remove 8/14/2001 10:40:23 AM
BLD00-02885 BLD-Final8/13/20018/14/20018/14/2001 12:00:00 AMAPASS
c/c#18770 8/14/2001 10:22:22 AM
MEC01-02395 Final8/13/20018/14/20018/14/2001 12:00:00 AMAFAIL
need 3/4" gas flex at rtu, pt ok 8/14/2001 1:28:47 PM
MEC01-02396 Rough-in8/13/20018/14/20018/14/2001 12:00:00 AMAFAIL
duct r.a. all the way to grill, and need 3/4" GAS flex at rtu, and remove fire caulking around fire dampers inside duct 8/14/2001 1:31:48 PM
MEC01-02396 Pressure Test8/13/20018/14/20018/14/2001 12:00:00 AMAPART
2 of 2 test ok, corrections on flexs 8/14/2001 1:30:17 PM
MEC01-01912 Final8/13/20018/14/20018/14/2001 12:00:00 AMAFAIL
remove fire caulking around fire dampers inside duct 8/14/2001 1:31:10 PM
MEC01-01122 Conference8/13/20018/14/20018/14/2001 12:00:00 AMAPASS
Al sparks ###-#### russ will also be going there am for conference
MEC01-02414 Final8/13/20018/14/20018/14/2001 12:00:00 AMPFAIL
pipe wh pop off drain to outdoors or into garage 8/14/2001 2:38:36 PM
MEC01-02414 Pressure Test8/13/20018/14/20018/14/2001 12:00:00 AMPCANC
witnessed by gas co. 8/14/2001 2:39:01 PM
MEC01-01926 Final8/14/20018/14/20018/14/2001 12:00:00 AMPFAIL
6" clearance at single wall flue connector 8/14/2001 4:00:29 PM
MEC01-01448 Final8/14/20018/14/20018/14/2001 12:00:00 AMPFAIL
need seperation between rtu flue and opening in next rtu 8/14/2001 3:34:50 PM
MEC01-02288 Rough-in8/14/20018/14/20018/14/2001 12:00:00 AMPPASS
4 on the north end ok 8/14/2001 2:55:22 PM
MEC01-01122 Rough-in8/14/20018/14/20018/14/2001 12:00:00 AMPFAIL
left c/n at construction trailer and with ymc foreman 8/14/2001 1:34:39 PM