Inspections for the day of: Wednesday, August 14, 2002.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-01238 FIRE-Final Inspection8/13/20028/14/20028/14/2002 12:00:00 AMAPART
temporary occ. given until fire extinguisher and smoke detector is corrected 8/14/2002 3:05:32 PM
BLD02-00691 FIRE-Sprinkler Rough-in8/13/20028/14/20028/14/2002 12:00:00 AMAFAIL
This inspection was done under FIR02-00215 but I left a correction notice for the addition of duct detectors, per review notes 3 and 18, per Don the general contractors request 8/14/2002 8:51:42 AM
BLD02-00567 FIRE-Final Inspection8/13/20028/14/20028/14/2002 12:00:00 AMACANC
cancelled per contractors request. Can not test the duct detectors due to wrong gas valves installed 8/14/2002 10:14:43 AM
FIR02-00215 INSP-Final Inspection8/14/20028/14/20028/14/2002 12:00:00 AMAFAIL
sprinkler heads in Comm Room 102 are overspaced for ordinary hazard occupancy (small room rule was used)
FIR01-00572 INSP-Final Inspection8/14/20028/14/20028/14/2002 12:00:00 AMPPASS
fire sprinkler finaled 8/14/2002 10:29:51 AM
FIR02-00117 INSP-Final Inspection8/14/20028/14/20028/14/2002 12:00:00 AMPFAIL
two sprinkler heads in the bakery cooler are too close to the lights so the lights or heads need to be relocated, tag sprinkler riser 8/14/2002 4:19:09 PM