BLD02-01238
| FIRE-Final Inspection | 8/13/2002 | 8/14/2002 | 8/14/2002 12:00:00 AM | A | PART |
|
|
temporary occ. given until fire extinguisher and smoke detector is corrected 8/14/2002 3:05:32 PM
|
BLD02-00691
| FIRE-Sprinkler Rough-in | 8/13/2002 | 8/14/2002 | 8/14/2002 12:00:00 AM | A | FAIL |
|
|
This inspection was done under FIR02-00215 but I left a correction notice for the addition of duct detectors, per review notes 3 and 18, per Don the general contractors request 8/14/2002 8:51:42 AM
|
BLD02-00567
| FIRE-Final Inspection | 8/13/2002 | 8/14/2002 | 8/14/2002 12:00:00 AM | A | CANC |
|
|
cancelled per contractors request. Can not test the duct detectors due to wrong gas valves installed 8/14/2002 10:14:43 AM
|
FIR02-00215
| INSP-Final Inspection | 8/14/2002 | 8/14/2002 | 8/14/2002 12:00:00 AM | A | FAIL |
|
|
sprinkler heads in Comm Room 102 are overspaced for ordinary hazard occupancy (small room rule was used)
|
FIR01-00572
| INSP-Final Inspection | 8/14/2002 | 8/14/2002 | 8/14/2002 12:00:00 AM | P | PASS |
|
|
fire sprinkler finaled 8/14/2002 10:29:51 AM
|
FIR02-00117
| INSP-Final Inspection | 8/14/2002 | 8/14/2002 | 8/14/2002 12:00:00 AM | P | FAIL |
|
|
two sprinkler heads in the bakery cooler are too close to the lights so the lights or heads need to be relocated, tag sprinkler riser 8/14/2002 4:19:09 PM
|