Inspections for the day of: Thursday, August 14, 2003.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-01458 FIRE-Final Inspection8/14/20038/14/20038/14/2003 12:00:00 AMAFAIL
Still no approved plans on site and the duct smoke detectors did not shut down the hvac units
FIR02-00487 INSP-Final Inspection8/11/20038/14/20038/14/2003 12:00:00 AMPPASS
fire alarm system finaled 8/14/2003 5:42:34 PM
BLD03-01335 FIRE-Final Inspection8/13/20038/14/20038/14/2003 12:00:00 AMPPART
A temporary occupancy was given with Dave Millers permission until the fire alarm system has been upgraded per the agreement with Boise Fire and Thorton Oliver 8/14/2003 1:56:34 PM
BLD03-01176 FIRE-Final Inspection8/13/20038/14/20038/14/2003 12:00:00 AMPFAIL
Provide building address, provide approved door hardware on south door, replace and test remote alarm LED 8/14/2003 1:41:51 PM
FIR03-00399 INSP-Final Inspection8/13/20038/14/20038/14/2003 12:00:00 AMPFAIL
mike; Phone #: ###-#### The sample tube duct smoke detectors that are being used for smoke damper operation are not listed for use on the 8" round duct, provide access to all dampers, test power supervision for the elevator, test the two duct smoke detectors being used for damper operation at the entrance to suite 200. All items tested are listed on the approved plans 8/14/2003 4:36:57 PM
BLD03-01053 FIRE-Final Inspection8/14/20038/14/20038/14/2003 12:00:00 AMPFAIL
Repair the emergency light by the breaker panel, install exit sign at the west door, provide approved door hardware for the electrical room, provide 4" address numbers, provide verification for requirements for hvac unit shutdown 8/14/2003 11:03:43 AM